| 2012-08-28 10:49:45 | 6751 NORTH JOG ROAD |
| | PERMIT #12080469 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. SMOKING SHALL BE PROHIBITED EXCEPT IN |
| | DESIGNATED EXTERIOR AREAS. ALL OTHER CONSTRUCTION AREAS |
| | SHALL HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR |
| | SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | SHEET 710-A2-100: COULD NOT LOCATE THE DOOR HARDWARE |
| | SET INFORMATION. INDICATE THE DOORS TO BE EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE. |
| | |
| | SHEET 710-A1-203: INDICATE THE INTERIOR FINISH |
| | CLASSIFICATION OF THE SUSPENDED CANOPIES LOCATED IN THE |
| | STAIR ENCLOSURE. |
| | |
| | SHEET 710-A5-100: THE PLAN DOES NOT INDICATE A SECOND |
| | EXIT FOR THE THIRD FLOOR; HOWEVER, THE PEDESTRIAN |
| | BRIDGE WOULD APPEAR TO FUNCTION AS THE SECONDARY MEANS |
| | OF EGRESS (HORIZONTAL EXIT). PROVIDE EXIT SIGNAGE FOR |
| | ENTRANCE INTO PEDESTRIAN BRIDGE. |
| | |
| | SHEET 710-A5-100: THE EMERGENCY LIGHTING IN THE STAIRS |
| | IS ONLY SHOWN ON THE THIRD FLOOR. |
| | |
| | SHEET 710-A5-100: THE MECHANICAL ROOM LOCATED WITHIN |
| | THE STAIR ENCLOSURE DOES NOT SHOW A FIRE RATING |
| | SEPARATING THIS ROOM FROM THE STAIR. |
| | |
| | SHEET 710-A5-100: INDICATE THE OCCUPANT LOAD FOR THE |
| | THIRD FLOOR ROOF/GARDEN AREA. |
| | |
| | SHEET 710-A5-100: THE NORTH LOBBY DOOR HAS A SWING THAT |
| | IS AGAINST THE FLOW OF EGRESS. |
| | |
| | PEDESTRIAN BRIDGE MAY NEED TO BE SEPARATED FROM THE |
| | VISITOR CENTER WITH A 2-HOUR FIRE BARRIER OR |
| | EQUIVALENT. REFERENCE THE FLORIDA BUILDING CODE SECTION |
| | 3104 FOR CODE REQUIREMENTS. |
| | |
| | DRAWINGS FOR THE ATTACHED PEDESTRIAN BRIDGE ARE |
| | REFERENCED ON THE DRAWINGS BUT DO NOT APPEAR TO HAVE |
| | BEEN SUBMITTED (710-A1-400, 710-A1-401 & 710-A3-400) |
| | |
| | SHEET 710-FP-100: PROVIDE SPEAKER/STROBE NOTIFICATION |
| | APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| | LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM |
| | NOTIFICATION BY VISIBLE SIGNALS AND VOICE |
| | ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA |
| | FIRE PREVENTION CODE - NFPA 101 |
| | |
| | SHEET 710-FP-100: PROVIDE A PRE-RECORDED FIRE ALARM |
| | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| | AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE |
| | ELEVATOR. |
| | |
| | SHEET 710-FP-100: PLANS DO NOT INDICATE THE METHOD |
| | (HEAT DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO |
| | SHUNT TRIP POWER TO THE ELEVATOR IN THE EVENT AN |
| | AUTOMATIC SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE |
| | ROOM. |
| | |
| | SHEET 710-FP-100: A CERTIFICATE OF COMPLETION AND A |
| | THIRD PARTY MONITORING/VERIFICATION (UL OR ETL) |
| | CERTIFICATE SHALL BE PROVIDED AT TIME OF FINAL FIRE |
| | ALARM INSPECTION. |
| | |
| | SHEET 710-FP-102: PROVIDE A MANUAL PULL STATION IN |
| | LOBBY #300. |
| | |
| | SHEET 710-FP-111: THE PEDESTRIAN BRIDGE IS LESS THAN |
| | 50% OPEN AND IS ATTACHED TO A THREE STORY BUILDING. |
| | PROVIDE SPRINKLER PROTECTION FOR BRIDGE PER FBC |
| | 903.6.1. |
| | |
| | SHEET 710-FP-111: SUBMIT HYDRAULIC CALCULATIONS FOR |
| | REVIEW. |
| | |
| | SHEET 710-FP-114: DESIGN SHALL CONFORM TO THE 2007 |
| | EDITION OF NFPA 13 NOT THE 2002 EDITION. |
| | |
| | SHEET 710-FP-114: PROVIDE LOCKING KNOX CAPS FOR THE |
| | FIRE DEPARTMENT CONNECTION. |
| | |