| 2012-10-30 11:54:49 | ****PROVISO**** |
| | ****PROVIDE AT INSPECTION**** |
| | ****REVISE PLAN AS NOTED**** |
| | ****ISSUED AT OWNER/BUILDER'S RISK**** |
| | |
| | ****REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S |
| | DISCRETION**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. FBC 107.2.1, ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 2. PLANS SPECIFY "STRAPS" - SEE FAC9N-3, PRODUCT |
| | APPROVAL REQUIRED FOR STRUCTURAL CONNECTORS, AND ALL |
| | ELEMENTS TO BE SPECIFIED TO SHOW RESISTANCE TO WIND |
| | LOADS FBC R 301.1, FBC 107.2.1. "STRAP" TO BE SPECIFIC |
| | TO A CONNECTOR WHICH CAN RESIST THE SPECIFIED DESIGN |
| | LOADS, PLEASE REVISE PLAN TO INCLUDE INFORMATION AND |
| | PROVIDE PRODUCT APPROVAL. |
| | |
| | 3. THE PLAN IS CUT OFF ON THE RIGHT SIDE, PLEASE SUBMIT |
| | COMPLETE LEGIBLE PLANS, FBC 107.2.1. |
| | |
| | 4. WALL FRAMING SPACING NOT INCLUDED IN PLAN (2X6 |
| | BEARING WALL). |
| | |
| | 5. RAFTER TIE IS NOTED ON THE PLAN, BUT NOT SHOWN |
| | GRAPHICALLY (SEC B-B), PROPOSED CONSTRUCTION NOT CLEAR |
| | FBC R 301.1, FBC 107.2.1. |
| | |
| | 6. INCLUDE WIND DESIGN CRITERIA, FBC R 301.1. THIS |
| | SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION. |
| | (170MPH EXPOSURE C). |
| | |
| | 7. PROVIDE WINDOW PRODUCT APPROVAL IN FIELD. IF THIS IS |
| | NOT AN IMPACT PRODUCT, IMPACT PROTECTION (SHUTTER) WILL |
| | BE REQUIRED. IF A SHUTTER IS USED, PROVIDE A PRODUCT |
| | APPROVAL FOR THE SHUTTER AS WELL. |
| | |
| | SEPARATE PERMIT REQUIRED FOR ROOF (APPLICATION AND |
| | PRODUCT APPROVAL) |
| | |
| | |
| | |