| 2012-08-30 14:34:45 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. FBC 107.2.1, ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 2. PLANS SPECIFY "STRAPS" - SEE FAC9N-3, PRODUCT |
| | APPROVAL REQUIRED FOR STRUCTURAL CONNECTORS, AND ALL |
| | ELEMENTS TO BE SPECIFIED TO SHOW RESISTANCE TO WIND |
| | LOADS FBC R 301.1, FBC 107.2.1. "STRAP" TO BE SPECIFIC |
| | TO A CONNECTOR WHICH CAN RESIST THE SPECIFIED DESIGN |
| | LOADS, PLEASE REVISE PLAN TO INCLUDE INFORMATION AND |
| | PROVIDE PRODUCT APPROVAL. |
| | |
| | 3. THE PLAN IS CUT OFF ON THE RIGHT SIDE, PLEASE SUBMIT |
| | COMPLETE LEGIBLE PLANS, FBC 107.2.1. |
| | |
| | 4. WALL FRAMING SPACING NOT INCLUDED IN PLAN (2X6 |
| | BEARING WALL). |
| | |
| | 5. RAFTER TIE IS NOTED ON THE PLAN, BUT NOT SHOWN |
| | GRAPHICALLY (SEC B-B), PROPOSED CONSTRUCTION NOT CLEAR |
| | FBC R 301.1, FBC 107.2.1. |
| | |
| | 6. INCLUDE WIND DESIGN CRITERIA, FBC R 301.1. THIS |
| | SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION. |
| | |
| | IF PLANS ARE NOT SIGNED AND SEALED BY A DESIGN |
| | PROFESSIONAL LICENSED UNDER FS471 OR FS481 (ENGINEER OR |
| | ARCHITECT), PLEASE ADDRESS THE FOLLOWING: |
| | |
| | 7. SEE FBC RESIDENTIAL 301.2.1.1, DESIGN IS TO BE IN |
| | ACCORDANCE WITH ONE OF THE METHODS LISTED. PLEASE |
| | SPECIFY AND REVISE PLAN TO INCLUDE DESIGN CRITERIA. |
| | |
| | IF USING A PRESCRIPTIVE METHOD, IT WOULD BE HELPFUL TO |
| | PLAN REVIEW TO INDICATE ON WHICH PAGES THESE DETAILS |
| | CAN BE LOCATED (ICC 600, AF & PA). |
| | |
| | IF USING ASCE 7-10, CALCULATINS MAY BE REQUIRED. |
| | |
| | |