Plan Review Notes
Plan Review Notes For Permit 12080390
Permit Number 12080390
Review Stop P
Sequence Number 2
Notes
Date Text
2012-09-17 13:47:02FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #2
 DENIED:
  
 COMMENTS NOTED, HOWEVER, PLEASE SEE SCOPING 213.3:
 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING FIXTURES
 AND ACCESSORIES PROVIDED IN A TOILET ROOM OR BATHING
 ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY WITH
 213.3.
  
 213.3.2 WATER CLOSETS. WHERE WATER CLOSETS ARE
 PROVIDED, AT LEAST ONE SHALL COMPLY WITH 604.
  
 FROM REVIEW #1:
  
 1. SHEETS A.3 AND A.4 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIEVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
 NOTE - OTHER CONFIGURATIONS ARE POSSIBLE AS LONG AS THE
 WATER CLOSET HAS A 5' CLEAR SPACE WITH THE LAVATORY IN
 THE SAME ROOM AND NOT IN THE CLEAR SPACE.
  
 2.
  
 3. SHEET A.6 THE PLUMBING (SANITARY) RISER DIAGRAM DOES
 NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  