| 2012-08-15 13:17:35 | FBC ACCESSIBILITY 2010 |
| | FBC PLUMBING 2010 REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEETS A.3 AND A.4 (1) SHOW AN NEW RESTROOM THAT |
| | DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010. |
| | THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1" |
| | WIDE TO ACHIEVE THE REQUIRED 5' CLEAR SPACE FOR THE |
| | WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1 |
| | THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC |
| | ACCESSIBILITY CODE 2010 604.3.2 |
| | NOTE - OTHER CONFIGURATIONS ARE POSSIBLE AS LONG AS THE |
| | WATER CLOSET HAS A 5' CLEAR SPACE WITH THE LAVATORY IN |
| | THE SAME ROOM AND NOT IN THE CLEAR SPACE. |
| | |
| | 2. BUSINESS OCCUPANCIES WITH OVER 15 OCCUPANTS REQUIRE |
| | DRINKING FOUNTAINS. FBC PLUMBING TABLE 403.1(E & F) |
| | SHEET A-1 SHOWS A FUTURE DRINKING FOUNTAIN. THE |
| | REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH FBC |
| | ACCESSIBILITY 2010. |
| | FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO |
| | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 3. SHEET A.6 THE PLUMBING RISER DIAGRAM DOES NOT SHOW |
| | THE DRINKING FOUNTAINS. |
| | |
| | 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING. |
| | FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3) |
| | |