Plan Review Notes
Plan Review Notes For Permit 12080390
Permit Number 12080390
Review Stop P
Sequence Number 1
Notes
Date Text
2012-08-15 13:17:35FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. SHEETS A.3 AND A.4 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIEVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
 NOTE - OTHER CONFIGURATIONS ARE POSSIBLE AS LONG AS THE
 WATER CLOSET HAS A 5' CLEAR SPACE WITH THE LAVATORY IN
 THE SAME ROOM AND NOT IN THE CLEAR SPACE.
  
 2. BUSINESS OCCUPANCIES WITH OVER 15 OCCUPANTS REQUIRE
 DRINKING FOUNTAINS. FBC PLUMBING TABLE 403.1(E & F)
 SHEET A-1 SHOWS A FUTURE DRINKING FOUNTAIN. THE
 REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH FBC
 ACCESSIBILITY 2010.
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3. SHEET A.6 THE PLUMBING RISER DIAGRAM DOES NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING.
 FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  