| 2012-08-26 13:45:31 | 210 SOUTH OLIVE AVENUE |
| | PERMIT #12080390 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PERMIT APPLICATION INDICATES THE ADDRESS IS 210 |
| | WHILE THE PLANS INDICATE AN ADDRESS OF 208 S OLIVE |
| | AVENUE. PLEASE CONFIRM THE CORRECT ADDRESS. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| | EXTINGUISHER COMPANY. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR CONSTRUCTION SHALL BE |
| | IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE |
| | SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND |
| | 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR |
| | AND BEAR THE LETTER "F" DESIGNATION PER FLORIDA STATUTE |
| | 633.027 AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| | DIAMETER SPHERE. |
| | |
| | PROVIDE HANDRAILS ON BOTH SIDES OF THE STAIR. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |