Plan Review Notes
Plan Review Notes For Permit 12080390
Permit Number 12080390
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-08-26 13:45:31210 SOUTH OLIVE AVENUE
 PERMIT #12080390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES THE ADDRESS IS 210
 WHILE THE PLANS INDICATE AN ADDRESS OF 208 S OLIVE
 AVENUE. PLEASE CONFIRM THE CORRECT ADDRESS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 STRUCTURES WITH LIGHT FRAME FLOOR CONSTRUCTION SHALL BE
 IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE
 SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND
 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR
 AND BEAR THE LETTER "F" DESIGNATION PER FLORIDA STATUTE
 633.027 AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 PROVIDE HANDRAILS ON BOTH SIDES OF THE STAIR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  