2012-08-17 16:42:4012080390
 210 S. OLIVE AVENUE
 COMMERCIAL INTERIOR REMODEL
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
 ELECTRICAL PANELS MAY NOT BE LOCATED IN STORAGE ROOMS.
 PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS
 WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL
 TIMES. NEC 110.26, 240.24
  