| Plan Review Notes For Permit 12080390 |
| Permit Number |
12080390 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-17 16:42:40 | 12080390 | | | 210 S. OLIVE AVENUE | | | COMMERCIAL INTERIOR REMODEL | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. | | | NEC 230.2, 230.71, 230.72 | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | ELECTRICAL PANELS MAY NOT BE LOCATED IN STORAGE ROOMS. | | | PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS | | | WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL | | | TIMES. NEC 110.26, 240.24 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|