| Plan Review Notes For Permit 12080323 |
| Permit Number |
12080323 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-13 09:53:06 | SPOKE WITH KRYSTAL. ALTHOUGH THE APPLICATION IS FOR | | | TOTAL DEMOLITION, THE PARKING GARAGE IN PHASE ONE WILL | | | BE FIRST TO GO. REALIZING THAT PENNY'S WILL CONTINUE TO | | | NEED POWER, AN ELECTRICAL PERMIT THAT WILL SAFE EACH | | | PHASE OF DEMOLITION WILL NEED TO BE PULLED. ELECTRICAL | | | INSPECTIONS CAN THEN SUFFICE FOR RELEASES OF PHASES. | | | PARKING GARAGE STILL LIVE ACCORDING TO KRYSTAL. | | | A GAS RELEASE FOR THE ENTIRE PROJECT OR HOW PENNY'S | | | WILL REMAIN LIVE FOR DEMOLITION SHOULD BE RECEIVED | | | PRIOR TO ANY PHASE RELEASE. | | | WATER METER RELEASES, THERE WILL BE MANY WATER METERS | | | ON THIS JOB THAT NEED TO BE PULLED OR KEPT. THIS CAN BE | | | ACCOMPLISHED BY THE PLUMBING CONTRACTOR YET SIGNED ON. | | | FIRE SPRINKLERS, NEED TO BE ADDRESSED. HOW WILL PENNY'S | | | REMAIN PROTECTED? THIS MAY NEED FIRE TO SIGN OFF. | | | NO POLLUTION PREVENTION PLAN IN APPLICATION. ENG. WILL | | | NEED THAT. | | | PLAN OUT FRONT UNDER "B". |
|