Plan Review Notes
Plan Review Notes For Permit 12080314
Permit Number 12080314
Review Stop B
Sequence Number 2
Notes
Date Text
2012-09-26 09:04:30BUILDING PLAN REVIEW
 PERMIT: 12080314
 ADD: 429 25TH ST
 CONT: TO BE DETERMINED
 TEL: (202) 375-4753
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 DESIGNER OF RECORD: RAFAEL A RODRIGUEZ AR0016608
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 SEPT. 26/ 2012
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. SEMI-COMPIED.
 COMMENT FROM 1ST REVIEW:
 SHEET A1, A2 & A5 THE RIGHT SIDE ELEVATION INDICATE THE
 USE OF ONLY ONE (EXTERIOR) STAIR WITH MULTIPLE DOOR AND
 WINDOW OPENINGS WITHIN TEN FEET OF THE STAIR & LANDING,
 PLEASE REVIEW SECTION 2010 FBC-B 1026.6 AND FIGURE
 1023.1 2007 FBC-B COMMENTARY FOR AREAS RESTRICTION OF
 NO WINDOWS AND AREAS WHERE 3/4 HOUR OPENING PROTECTIVES
 CAN OCCUR.
 COMMENT FROM 2ND REVIEW: FROM BOTH RESIDENTIAL UNITS
 FROM THE SECOND FLOOR THEY SHARE A SINGLE EXIT EXTERIOR
 STAIRWAY. FROM UNIT B THE OCCUPANTS STILL HAVE TO
 TRAVEL PAST UNPROTECTED OPENINGS WITHIN 10 FT OF
 UNPROTECTED OPENINGS. 2010 FBC-B 1026.1 & TABLE 715.4.
  
 4) 2ND REQUEST. SHEET A1 1ST FLOOR FRONT WINDOWS THAT
 FACE 25TH STREET, WINDOW TYPE "A" FIVE UNITS WITH A
 STRUCTURAL MULLION 6"X2"X3/8" STRUCTURAL TUBE STEEL,
 ALSO SHOWN ON SHEET S-1 COLOUMN HEADING SC-2 HSS
 6X2X3/8 STEEL TUBE THE DETAIL INDICATES TTHE USE OF (2)
 5/8"X9" J-BOLTS ASSUMED FOR THE BOTTOM STEEL PLATE,
 UNDER THE HEADING "REMARKS" IT INDICATES WEDGE ANCHORS
 ARE ACCEPTABLE WITH NO MINIMUM DIMENSIONS REQUIRED FOR
 THE WEDGE ANCHOR. THE STRUCTURAL STEEL TUBES ARE TO BE
 CONSIDERED AS PART OF THE (MWFRS) MAIN WIND FORCE
 RESISTING SYSTEM 1609.6.4.DESIGN PROCEDURES, NOT ONLY
 DO THESE COLUMNS PROVIDE STRENGHT FOR THE BEAM ABOVE
 WHERE BLOCK WAS REMOVED, AND A CONTINIOUS LOAD PATH
 (MWFRS), BUT THEY WILL PROVIDE A STRUCTURAL ELEMENT FOR
 THE WINDOWS AND DOORS TO ANCHOR TO SECTION 1715.5.4.1
 ANCHORING REQUIREMENTS- WINDOWS AND DOORS.
  
 5) COMPLIED.
  
 6) 2ND REQUEST. SHEET A1 DOOR #2 INDICATES THE
 ACCESSIBLE PATH BEING 48 INCHES WIDE BUT IS REDUCED TO
 ONLY 42 INCHES AT RAMP AND THE UPPER LANDING LEADING
 INTO DOOR # 02. PLEASE REVIEW MANEUVERING CLEARENCES AT
 DOORS ACCESSIBILITY CODE FIGURE 404.2.4.1 (H) REQUIRES
 A 48 INCHES CLEAR.
  
 7A) COMPLIED.
  
 7B) PLEASE PROVIDE A CONTRACT BREAKDOWN FOR FIRST FLOOR
 VALUE, CONTRACT VALUE ON PERMIT APPLICATION INDICATES A
 WORK VALUE OF $45, 000.00 THIS AMOUNT OF MONEY SEES LOW
 FOR THE AMOUNT OF WORK BEING COMPLETED UNDER THIS
 PERMIT 109.3BUILDING PERMIT VALUATIONS. PLEASE REVUE
 SECTION ACCESSIBILITY CODE 202.4.1 / 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISSPROPORTIONALITY. THE
 CONTRACTOR TO PROVIDE DOCUMENTATION WHERE 20% OF THE
 FUNDS WILL BE USED IN BRINGING THIS BUILDING UP TO THE
 CURRENT ACCESSIBILITY CODE THE DOOR WAY LEADING TO
 RESTROOM ROOM # 106 MAY OR MAY NOT NEED TO BE WIDENED
 TO COMPLY WITH THE CODE.
  
 8) 2ND REQUEST. SHEET A1 INDICATES A SINGLE DRINKING
 FOUNTAIN PLEASE REVIEW ACCESSIBILITY CODE SECTION 602.1
 DRINKING FOUNTAINS SHALL COMPLY WITH 307 & 602. COMMENT
 FROM 2ND REVIEW PLEASE DIPICT A 2 BOWL DRINKING
 FOUNTAIN FOR HIGH AND LOW USE, AS INDICATED ON PLAN IT
 APPEARS A SINGLE BOWL USE IS ACCEPTABLE.
  
 9) 2ND REQUEST; SEMI-COMPLIED. PLEASE NOTE: WINDOW AND
 DOOR PRODUCT APPROVALS SUBMITTED MEET WIND LOADING
 REQUIREMENTS BUT SOME OF THESE OPENINGS WILL NEED TO
 MEET ADDITIONAL REQUIREMENTS AS FIRE RATINGS THAT WILL
 EFFECT LARGE MISSILE TESTING AND REQUIRE STORM SHUTTER
 PROTECTION. WINDOWS WITH 45 MINUTE FIRE RATING
 REQUIREMENTS 2010 FBC-B 1026.6 AND FIGURE 1023.1 2007
 FBC-B COMMENTARY.
 COMMENT FROM 2ND REVIEW: STORM SHUTTER REPORT WAS
 SUBMITTED, ACCORDIAN SHUTTER, PLEASE CIRCLE TYPES OF
 INSTALATIONS TO BE USED IN THE INSTALATION, TYPE OF
 ANCHORS,
 TYPE OF MATERIALS ANCHORS WILL BE INSTALLED IN, TYPE OF
 ANCHOR AND SPACING FOR SPAN OF SHUTTER. COMPONENTS &
 CLADDING 1609.1.2.PROTECTION OF OPENINGS.
  
 10) COMPLIED,
  
 11) 2ND REQUEST: ROOFING PRODUCT APPROVAL NOA
 11-0601.09 & 12-0227.18 NONE OF THE SUB-SYSTEMS AND OR
 OPTIONS WERE HIGHLIGHTED, LIMITATION # 7 IN EFFECT
 REQUIRING A DESIGN PROFESSIONAL TO PROVIDE CALCULATIONS
 FOR ENHANCED FASTENING IN ZONES 2 & 3.
  
 12) 2ND REQUEST: NOA 11-1013.24 IS A PGT OUTSWING
 ALUMINUN OUTSWING FRENCH DOOR SYSTEM, WHEREAS THE PLANS
 SHEET A1 INDICATE THE USE OF A INSWING DOOR.1609.1.2/
 RULE RULE 9N-3(31) DOORS, & ADDITIONAL INFORMATION
 REQUIRED 107.2.1.3.
  
 13) 2ND REQUEST: PRODUCT TESTING SHEETS FOR TRULITE
 INDICATE THEY ARE TESTED TO THE FLORIDA APPROVAL
 SYSTEM, PLEASE PROVIDE DOCUMENATION THIS PRODUCT HAS
 BEEN TESTED WITH THIS TESTING AGENCY. RULE 9N3 (31).
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  