Plan Review Notes
Plan Review Notes For Permit 12080313
Permit Number 12080313
Review Stop P
Sequence Number 2
Notes
Date Text
2012-10-05 10:48:33FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #2
 DENIED:
  
 1. SHEETS A-1 AND A-8 (1) PARTIALLY COMPLIED:
 FBC ACCESSIBILITY CODE 2010 604.2 LOCATION. THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES
 (455 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION.
  
 2. ***PROVISO***
 IF A SINGLE DRINKING FOUNTAIN IS TO BE USED IT MUST
 COMPLY WITH 602.1 THROUGH 602.6 AND 602.7. A CUP HOLDER
 DOES NOT COMPLY WITH 211.2
  
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3.
  
 4.
  
 ***NOTE***
 IRRIGATION IS NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, DRAWING, REVIEW, AND FEE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676