Plan Review Notes
Plan Review Notes For Permit 12080313
Permit Number 12080313
Review Stop P
Sequence Number 1
Notes
Date Text
2012-08-15 11:02:36FBC ACCESSIBILITY 2010
 FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. SHEETS A-1 AND A-8 (1) SHOW AN NEW RESTROOM THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1"
 WIDE TO ACHIVE THE REQUIRED 5' CLEAR SPACE FOR THE
 WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC
 ACCESSIBILITY CODE 2010 604.3.2
  
 2. SHEETS A-1 AND A-8 (1) SHOW A DRINKING FOUNTAIN THAT
 DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010.
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3. SHEET A-3 THE PLUMBING RISER DIAGRAM DOES NOT SHOW
 THE DRINKING FOUNTAINS.
  
 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING.
 FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3)
  
 ***NOTE***
 IRRIGATION IS NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, DRAWING, REVIEW, AND FEE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved