| Plan Review Notes For Permit 12080313 |
| Permit Number |
12080313 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-15 11:02:36 | FBC ACCESSIBILITY 2010 | | | FBC PLUMBING 2010 REVIEW #1 | | | DENIED: | | | | | | 1. SHEETS A-1 AND A-8 (1) SHOW AN NEW RESTROOM THAT | | | DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010. | | | THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF 7'-1" | | | WIDE TO ACHIVE THE REQUIRED 5' CLEAR SPACE FOR THE | | | WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1 | | | THE LAVATORY WILL NOT BE PERMITTED IN THE 5' SPACE. FBC | | | ACCESSIBILITY CODE 2010 604.3.2 | | | | | | 2. SHEETS A-1 AND A-8 (1) SHOW A DRINKING FOUNTAIN THAT | | | DOES NOT COMPLY WITH FBC ACCESSIBILITY 2010. | | | FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO | | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | | | | 3. SHEET A-3 THE PLUMBING RISER DIAGRAM DOES NOT SHOW | | | THE DRINKING FOUNTAINS. | | | | | | 4. PLEASE INCLUDE THE WATER PIPE IN THE DRAWING. | | | FBC 2010 LOCAL AMENDMENTS 107.3.5.1.3 PLUMBING (3) | | | | | | ***NOTE*** | | | IRRIGATION IS NOT PART OF THIS REVIEW. SEPARATE | | | APPLICATION, DRAWING, REVIEW, AND FEE REQUIRED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 |
|