Plan Review Notes
Plan Review Notes For Permit 12080313
Permit Number 12080313
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-08-30 10:55:59927 25TH STREET
 PERMIT #12080314 (FIRST FLOOR)
 PERMIT #12080313 (SECOND FLOOR)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1: STORAGE OCCUPANCIES SHALL BE SEPARATED FROM
 OTHER OCCUPANCIES SUCH AS MERCANTILE, WITH A 2-HOUR
 FIRE BARRIER PER TABLE 6.1.14.4.1B (NFPA 101).
  
 SHEET A-4: ONLY ONE MEANS OF EGRESS IS PROVIDED FROM
 THE THIRD FLOOR ROOFTOP AREA. THIS DESIGN RESULTS IN A
 COMMON PATH OF TRAVEL GREATER THAN 35 FEET (REFERENCE
 SECTION 30.2.3.5.1 NFPA 101).
  
 SHEET A-4: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR.
  
 ALL DOORS/WINDOWS/OPENINGS LOCATED WITHIN 10 FEET
 HORIZONTALLY (AND BELOW) THE EXTERIOR STAIR SHALL HAVE
 A 45-MINUTE FIRE RESISTANCE RATING PER SECTIONS
 7.2.2.6.3 AND 7.2.2.6.4 OF NFPA 101.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  