| 2012-08-30 10:55:59 | 927 25TH STREET |
| | PERMIT #12080314 (FIRST FLOOR) |
| | PERMIT #12080313 (SECOND FLOOR) |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A-1: STORAGE OCCUPANCIES SHALL BE SEPARATED FROM |
| | OTHER OCCUPANCIES SUCH AS MERCANTILE, WITH A 2-HOUR |
| | FIRE BARRIER PER TABLE 6.1.14.4.1B (NFPA 101). |
| | |
| | SHEET A-4: ONLY ONE MEANS OF EGRESS IS PROVIDED FROM |
| | THE THIRD FLOOR ROOFTOP AREA. THIS DESIGN RESULTS IN A |
| | COMMON PATH OF TRAVEL GREATER THAN 35 FEET (REFERENCE |
| | SECTION 30.2.3.5.1 NFPA 101). |
| | |
| | SHEET A-4: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE |
| | STAIR. |
| | |
| | ALL DOORS/WINDOWS/OPENINGS LOCATED WITHIN 10 FEET |
| | HORIZONTALLY (AND BELOW) THE EXTERIOR STAIR SHALL HAVE |
| | A 45-MINUTE FIRE RESISTANCE RATING PER SECTIONS |
| | 7.2.2.6.3 AND 7.2.2.6.4 OF NFPA 101. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |