| Plan Review Notes For Permit 12080296 |
| Permit Number |
12080296 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-09-24 16:36:48 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | ALUMINUM METAL ROOF FL#5286.1 IS FOR THE 2007 FBC AND | | | HAS A MAXIMUM DESIGN UPLIFT PRESSURE OF -69.25 PSF | | | WHICH IS TOO LOW FOR A STRUCTURE WITH A 4/12 SLOPE ROOF | | | AND A 20 ' PLUS MEAN ROOF HEIGHT LOCATED IN EXPOSURE | | | CATEGORY D WITH A 170 MPH WINDSPEED ( VULT 170 MPH/ | | | VASD 132 MPH) . ALSO THE PLANS SPECIFY THIS AS A COPPER | | | ROOF. PLEASE PROVIDE THE APPROPRIATE PRODUCT APPROVALS. | | | DCA RULE 9N-3 AND FBC R301.2.1 | | | | | | 2) SUBMIT TWO COPIES OF EVALUATION REPORTS FOR THE | | | SPRAY FOAM INSULATION THAT WILL BE INSTALLED. | | | | | | 3) SPECIFY THE METHOD OF ATTACHMENT LISTED IN THE | | | CEMENT ROOF TILE PRODUCT APPROVAL THAT WILL BE USED TO | | | INSTALL THE ROOF TILE AND RESIST THE OVERTURN MOMENT. | | | FBC R 301.2.1 AND FBC R905.3 | | | | | | 4) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING OF THE CORNER AND | | | PERIMETER AREAS AS REQUIRED BY LIMITATION #7 OF THE | | | PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF SYSTEM WITH | | | THE -52.5 PSF DESIGN PRESSURE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|