Plan Review Notes
Plan Review Notes For Permit 12080296
Permit Number 12080296
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-16 08:07:502010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WHICH
 REQUIRES THE LOWEST FINISHED FLOOR TO HAVE A MINIMUM
 ELEVATION OF 7'6" BASE FLOOD ELEVATION. THIS INCLUDES
 THE 6" FREEBOARD ESTABLISHED BY THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE. SPECIFY THE FINISH FLOOR
 ELEVATIONS FOR THE EXISTING STRUCTURE AND THE PROPOSED
 ADDITION ON THE PLANS AND SUBMIT A ELEVATION
 CERTIFICATE FOR THE PROPOSED ADDITION. WPB CODE OF
 ORDINANCES CHAPTER 94, ARTICLE XVII SECTIONS 94-541
 THRU 94-547.
  
 2) ON SHEET A-1 THE COVERED ENTRY IS MISLABELED AS
 BEDROOM #2. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 3) THE PROJECT IS LOCATED IN AN AREA OF QUESTIONABLE
 SOIL. SUBMIT TWO SIGNED AND SEALED COPIES OF A
 SUBSURFACE SOILS REPORT FOR THE PROJECT. FBC R401.4
  
 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS SIGNED BY THE
 PREPARER AND THE OWNER/AGENT FOR THE ADDED AREAS OF
 CONDITIONED SPACE AS REQUIRED BY 2010 FBC ENERGY
 CONSERVATION SECTION 402.
  
 5) THE PLANS SPECIFY "POLYISOCENE" INSULATION. DO YOU
 MEAN "POLYICYNENE" SPRAY FOAM INSULATION? SUBMIT TWO
 SETS OF THE EVALUATION REPORTS FOR THE SPRAY FOAM
 INSULATION AND SPECIFY THAT THE ATTIC IS UNVENTED ON
 THE PLANS. FBC R316
  
 6) THE BALCONY GUARDS ARE SPECIFIED AS 32" IN HEIGHT.
 FBC R 312.2 REQUIRES THE GUARDS TO BE A MINIMUM OF 36"
 ABOVE THE WALKING SURFACE. PLEASE CORRECT.
  
 7) SHOW COMPLIANCE WITH FBC R312.3 WHICH REQUIRES THAT
 OPENINGS IN THE GUARDS CAN NOT ALLOW A 4" DIAMETER
 SPHERE TO PASS.
  
 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS (NOA NO. 08-1210.03) AND THE
 OUTSWING DOORS (NOA NO. 11-0912.12) HAVE BEEN
 SUPERSEDED. PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT
 APPROVALS FOR THE SINGLE HUNG WINDOWS AND THE OUTSWING
 DOORS. DCA RULE 9N-3
  
 10) PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT APPROVALS
 FOR THE FIXED GLASS WINDOWS, THE STRUCTURAL MULLIONS,
 THE CONCRETE ROOF TILES (SPECIFY ATTACHMENT METHOD) THE
 STANDING SEAM METAL ROOF, THE MODIFIED BITUMEN ROOFING
 ON THE BALCONIES (WITH RAS 117 ENHANCED FASTENING
 CALCULATIONS) AND THE SIMPSON CONNECTORS, STRAPS &
 HANGERS AS REQUIRED BY DCA RULE 9N-3.
  
 11) IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE
 BEEN ADDRESSED.
  