| 2012-08-16 08:07:50 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WHICH |
| | REQUIRES THE LOWEST FINISHED FLOOR TO HAVE A MINIMUM |
| | ELEVATION OF 7'6" BASE FLOOD ELEVATION. THIS INCLUDES |
| | THE 6" FREEBOARD ESTABLISHED BY THE CITY OF WEST PALM |
| | BEACH'S FLOOD ORDINANCE. SPECIFY THE FINISH FLOOR |
| | ELEVATIONS FOR THE EXISTING STRUCTURE AND THE PROPOSED |
| | ADDITION ON THE PLANS AND SUBMIT A ELEVATION |
| | CERTIFICATE FOR THE PROPOSED ADDITION. WPB CODE OF |
| | ORDINANCES CHAPTER 94, ARTICLE XVII SECTIONS 94-541 |
| | THRU 94-547. |
| | |
| | 2) ON SHEET A-1 THE COVERED ENTRY IS MISLABELED AS |
| | BEDROOM #2. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| | |
| | 3) THE PROJECT IS LOCATED IN AN AREA OF QUESTIONABLE |
| | SOIL. SUBMIT TWO SIGNED AND SEALED COPIES OF A |
| | SUBSURFACE SOILS REPORT FOR THE PROJECT. FBC R401.4 |
| | |
| | 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS SIGNED BY THE |
| | PREPARER AND THE OWNER/AGENT FOR THE ADDED AREAS OF |
| | CONDITIONED SPACE AS REQUIRED BY 2010 FBC ENERGY |
| | CONSERVATION SECTION 402. |
| | |
| | 5) THE PLANS SPECIFY "POLYISOCENE" INSULATION. DO YOU |
| | MEAN "POLYICYNENE" SPRAY FOAM INSULATION? SUBMIT TWO |
| | SETS OF THE EVALUATION REPORTS FOR THE SPRAY FOAM |
| | INSULATION AND SPECIFY THAT THE ATTIC IS UNVENTED ON |
| | THE PLANS. FBC R316 |
| | |
| | 6) THE BALCONY GUARDS ARE SPECIFIED AS 32" IN HEIGHT. |
| | FBC R 312.2 REQUIRES THE GUARDS TO BE A MINIMUM OF 36" |
| | ABOVE THE WALKING SURFACE. PLEASE CORRECT. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R312.3 WHICH REQUIRES THAT |
| | OPENINGS IN THE GUARDS CAN NOT ALLOW A 4" DIAMETER |
| | SPHERE TO PASS. |
| | |
| | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SINGLE HUNG WINDOWS (NOA NO. 08-1210.03) AND THE |
| | OUTSWING DOORS (NOA NO. 11-0912.12) HAVE BEEN |
| | SUPERSEDED. PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT |
| | APPROVALS FOR THE SINGLE HUNG WINDOWS AND THE OUTSWING |
| | DOORS. DCA RULE 9N-3 |
| | |
| | 10) PLEASE SUBMIT 2 SETS OF CURRENT PRODUCT APPROVALS |
| | FOR THE FIXED GLASS WINDOWS, THE STRUCTURAL MULLIONS, |
| | THE CONCRETE ROOF TILES (SPECIFY ATTACHMENT METHOD) THE |
| | STANDING SEAM METAL ROOF, THE MODIFIED BITUMEN ROOFING |
| | ON THE BALCONIES (WITH RAS 117 ENHANCED FASTENING |
| | CALCULATIONS) AND THE SIMPSON CONNECTORS, STRAPS & |
| | HANGERS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 11) IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE |
| | BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |