| Plan Review Notes For Permit 12080215 |
| Permit Number |
12080215 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-10-15 17:49:00 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. IT IS NOT CLEAR HOW WIND PRESSURES HAVE BEEN | | | DETERMINED; COMPONENTS & CLADDING OR MWFRS? PRESSURES | | | TOO LOW FOR COMPONENTS & CLADDING, SEE FBC RESIDENTIAL | | | 301.1. | | | | | | 2ND REVIEW, ZONES 1 AND 3 PRESSURES TOO LOW BASED ON | | | TABLE, FBC R 301.2(2) AND (3). | | | | | | 2. OK | | | | | | 3. SEPARATE ROOF PERMIT IS REQUIRED, INFORMATIONAL | | | ONLY. | | | | | | 4. OK | | | | | | 5. (NEW COMMENT) PROVIDE STAIR DIMENSIONS, SEE FBC R | | | 311.7.4. IT IS NOT CLEAR WHAT THE 6" DIMENSION REFERS | | | TO, BUT DOES NOT COMPLY FOR EITHER TREAD OR RISER. | | | | | | | | | |
|