2012-10-15 17:49:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IT IS NOT CLEAR HOW WIND PRESSURES HAVE BEEN
 DETERMINED; COMPONENTS & CLADDING OR MWFRS? PRESSURES
 TOO LOW FOR COMPONENTS & CLADDING, SEE FBC RESIDENTIAL
 301.1.
  
 2ND REVIEW, ZONES 1 AND 3 PRESSURES TOO LOW BASED ON
 TABLE, FBC R 301.2(2) AND (3).
  
 2. OK
  
 3. SEPARATE ROOF PERMIT IS REQUIRED, INFORMATIONAL
 ONLY.
  
 4. OK
  
 5. (NEW COMMENT) PROVIDE STAIR DIMENSIONS, SEE FBC R
 311.7.4. IT IS NOT CLEAR WHAT THE 6" DIMENSION REFERS
 TO, BUT DOES NOT COMPLY FOR EITHER TREAD OR RISER.
  
  
  