| 2012-08-14 15:12:42 | 12080192 | | | 275 @ N QUADRILLE BLVD. | | | QUADRILLE STREETSCAPE | | | | | | SHEET E-4 | | | PROVIDE AN ELECTRICAL SYSTEM BONDING AND GROUNDING | | | SCHEMATIC FOR THE ELECTRICAL SERVICE. NEC 250.4, 250.20 | | | | | | SHEET E-5 | | | PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION | | | FOR THE SITE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010 | | | FBC 1609.1., ASCE 7-10 | | | | | | REVISE PLAN DISCREPANCY FOR WIND LOADING TO INDICATE | | | THE CURRENT FLORIDA BUILDING CODE (FBC) 2010. PROVIDE | | | AN EXPOSURE CATEGORY AND IMPORTANCE FACTOR TO THE | | | DESIGN. FBC 1609, ASCE 7-10 | | | | | | NOTE: PLANS FOR NEW CONSTRUCTION SHALL BE SIGNED BY THE | | | DESIGNER OF RECORD. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|