| Plan Review Notes For Permit 12080187 |
| Permit Number |
12080187 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-15 19:32:34 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE A WINDOW | | | SCHEDULE AS TWO DIFFERENT PRODUCT APPROVALS WERE | | | SUBMITTED, ONE FOR IMPACT AND ONE FOR NON IMPACT. | | | | | | 2. . IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | | PROVIDE CALCULATIONS. | | | | | | 3. MULLION PRODUCT APPROVAL REQUIRED FAC 9N-3. | | | | | | 4. PLEASE PROVIDE TWO COMPLETE SETS OF PLANS AND | | | PRODUCT APPROVALS. FAILURE TO PROVIDE TWO SETS WILL | | | RESULT IN AN ADMIN/COPY FEE BEING ADDED TO YOUR PERMIT. | | | | | | | | | | | | |
|