Plan Review Notes
Plan Review Notes For Permit 12080184
Permit Number 12080184
Review Stop M
Sequence Number 1
Notes
Date Text
2012-08-08 08:59:522010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE SCOPE OF WORK ON THE SUBMITTED PLANS INDICATES
 THAT NEW A/C SYSTEMS WILL BE INSTALLED. SUBMIT
 MECHANICAL PLANS THAT INDICATE THE LOCATION AND SIZES
 OF THE DUCTWORK, THE SUPPLY AND RETURN GRILL SIZES AND
 THE CFMS AT EACH SUPPLY OUTLET. SPECIFY THE EQUIPMENT
 LOCATIONS AND PROVIDE AN EQUIPMENT SCHEDULE FOR EACH
 BUILDING ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) SUBMIT TWO COPIES OF HEATING AND COOLING SIZING
 CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL S BASED ON
 BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA
 MANUAL J OR OTHER APPROVED METHODS FOR EACH BUILDING.
 FBCR M1401.3
  
 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS IN COMPLIANCE
 WITH THE 2010 FBC ENERGY CONSERVATION CHAPTER 4.
  