| Plan Review Notes For Permit 12080184 |
| Permit Number |
12080184 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-08 08:59:52 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE SCOPE OF WORK ON THE SUBMITTED PLANS INDICATES | | | THAT NEW A/C SYSTEMS WILL BE INSTALLED. SUBMIT | | | MECHANICAL PLANS THAT INDICATE THE LOCATION AND SIZES | | | OF THE DUCTWORK, THE SUPPLY AND RETURN GRILL SIZES AND | | | THE CFMS AT EACH SUPPLY OUTLET. SPECIFY THE EQUIPMENT | | | LOCATIONS AND PROVIDE AN EQUIPMENT SCHEDULE FOR EACH | | | BUILDING ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) SUBMIT TWO COPIES OF HEATING AND COOLING SIZING | | | CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL S BASED ON | | | BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA | | | MANUAL J OR OTHER APPROVED METHODS FOR EACH BUILDING. | | | FBCR M1401.3 | | | | | | 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS IN COMPLIANCE | | | WITH THE 2010 FBC ENERGY CONSERVATION CHAPTER 4. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|