2012-08-08 17:04:58PROVISIO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
  
  