Plan Review Notes
Plan Review Notes For Permit 12080184
Permit Number 12080184
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-08 09:24:062010 FBC
  
 DENIED BY BUILDING
  
 1) THE VALUE FOR THE SCOPE OF WORK INDICATED BY THE
 PLANS APPEARS TO BE UNDERESTIMATED ON THE PERMIT
 APPLICATION. THE PLANS INDICATE ADDING A BATHROOM
 INSIDE EXISTING SPACE, REPLACING PLUMBING FIXTURES,
 ADDING NEW A/C TO BOTH STRUCTURES, REPLACING KITCHEN
 CABINETS, INSTALLING NEW ELECTRIC SERVICE AND WIRING,
 INSTALLING INSULATION AND DRYWALL, INSTALLING NEW
 IMPACT RATED WINDOWS AND NEW BARREL TILE ROOF OVER THE
 ENCLOSED PORCH AND CONVERTING THE GARAGE AREA OF THE
 GUEST HOUSE TO LIVING AREA. SUBMIT 2 COPIES OF A
 DETAILED COST BREAK DOWN FOR EACH ITEM LISTED INCLUDING
 LABOR AND MATERIAL COSTS ALSO AND INCLUDE COST DESIGN
 FEES, OVERHEAD AND PROFIT. CITY AMENDMENTS 109.3
  
 2) BASED OF THE PROPERTY APPRAISER'S RECORDS THERE IS A
 216 SQUARE FOOT GARAGE THAT FORMS PART OF THE GUEST
 HOUSE. UNLESS PROOF CAN BE PROVIDED THAT THE GARAGE WAS
 CONVERTED TO LIVING SPACE WITH THE PROPER PERMITS AND
 INSPECTIONS, IT WILL BE CONSIDERED AS A GARAGE AND
 COUNTY IMPACT FEES MAY BE CHARGED WHEN CONVERTING TO
 LIVING SPACE. PROVIDE AREA TABULATIONS FOR EACH OF THE
 STRUCTURES ON THE PLANS. CITY AMENDMENTS 107.2.1.3
  
 3) SPECIFY THE DESIGN CRITERIA (WINDSPEED & EXPOSURE
 CATEGORY) ON THE PLANS. FBC R301.2.1.1
  
 4) PROVIDE DIMENSIONED FLOOR PLAN OF THE NEW BATHROOM
 IN THE MAIN HOUSE SHOWING COMPLIANCE WITH FBC R307.1.
  
 5) PROVIDE WALL SECTIONS FOR ALL NEW AND EXISTING
 BEARING AND NON-BEARING WALLS. CITY AMENDMENTS 107.2.1
  
 6) SHOW COMPLIANCE WITH FBC R310.1 EMERGENCY ESCAPE AND
 RESCUE OPENING AT THE BEDROOM THAT WAS CONVERTED FROM A
 GARAGE.
  
 7) SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE WITH
 2010 FBC ENERGY CONSERVATION CHAPTER 4 FOR EACH
 BUILDING.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 BARREL TILE ROOFING AS REQUIRED BY DCA RULE 9N-3.
 SPECIFY THE FASTENING METHOD FROM THE PRODUCT APPROVAL
 THAT WILL BE USED TO INSTALL THE ROOF TILE. IF POLYFOAM
 WILL BE USED, SUBMIT PRODUCT APPROVALS FOR IT. FBC
 R905.3
  
 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT WILL BE INSTALLED AS
 REQUIRED BY DCA RULE 9N-3.
  
 10) THE PLANS SPECIFY IMPACT RESISTANT WINDOWS,
 HOWEVER, THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 FOR NON-IMPACT RESISTANT WINDOWS. FBC EXISTING BUILDING
 606.4 AND FBC R301.2.1.2 REQUIRES GLAZED OPENINGS TO BE
 PROTECTED FROM WINDBOURNE DEBRIS. THE IMPACT PROTECTION
 DEVICES SHALL MEET THE LARGE MISSILE TEST OF ASTM E
 1996, ASTM E 1886, SSTD 12 OR TAS 201, 202 AND 203 OR
 AAMA 506. SUBMIT PRODUCT APPROVALS FOR THE IMPACT
 PROTECTION DEVICES. INCLUDE A KEY PLAN AND AN
 INSTALLATION SCHEDULE WITH ANCHOR TYPE AND SPACING.
  
 11) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE
 REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]