| 2012-08-08 09:24:06 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE VALUE FOR THE SCOPE OF WORK INDICATED BY THE |
| | PLANS APPEARS TO BE UNDERESTIMATED ON THE PERMIT |
| | APPLICATION. THE PLANS INDICATE ADDING A BATHROOM |
| | INSIDE EXISTING SPACE, REPLACING PLUMBING FIXTURES, |
| | ADDING NEW A/C TO BOTH STRUCTURES, REPLACING KITCHEN |
| | CABINETS, INSTALLING NEW ELECTRIC SERVICE AND WIRING, |
| | INSTALLING INSULATION AND DRYWALL, INSTALLING NEW |
| | IMPACT RATED WINDOWS AND NEW BARREL TILE ROOF OVER THE |
| | ENCLOSED PORCH AND CONVERTING THE GARAGE AREA OF THE |
| | GUEST HOUSE TO LIVING AREA. SUBMIT 2 COPIES OF A |
| | DETAILED COST BREAK DOWN FOR EACH ITEM LISTED INCLUDING |
| | LABOR AND MATERIAL COSTS ALSO AND INCLUDE COST DESIGN |
| | FEES, OVERHEAD AND PROFIT. CITY AMENDMENTS 109.3 |
| | |
| | 2) BASED OF THE PROPERTY APPRAISER'S RECORDS THERE IS A |
| | 216 SQUARE FOOT GARAGE THAT FORMS PART OF THE GUEST |
| | HOUSE. UNLESS PROOF CAN BE PROVIDED THAT THE GARAGE WAS |
| | CONVERTED TO LIVING SPACE WITH THE PROPER PERMITS AND |
| | INSPECTIONS, IT WILL BE CONSIDERED AS A GARAGE AND |
| | COUNTY IMPACT FEES MAY BE CHARGED WHEN CONVERTING TO |
| | LIVING SPACE. PROVIDE AREA TABULATIONS FOR EACH OF THE |
| | STRUCTURES ON THE PLANS. CITY AMENDMENTS 107.2.1.3 |
| | |
| | 3) SPECIFY THE DESIGN CRITERIA (WINDSPEED & EXPOSURE |
| | CATEGORY) ON THE PLANS. FBC R301.2.1.1 |
| | |
| | 4) PROVIDE DIMENSIONED FLOOR PLAN OF THE NEW BATHROOM |
| | IN THE MAIN HOUSE SHOWING COMPLIANCE WITH FBC R307.1. |
| | |
| | 5) PROVIDE WALL SECTIONS FOR ALL NEW AND EXISTING |
| | BEARING AND NON-BEARING WALLS. CITY AMENDMENTS 107.2.1 |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R310.1 EMERGENCY ESCAPE AND |
| | RESCUE OPENING AT THE BEDROOM THAT WAS CONVERTED FROM A |
| | GARAGE. |
| | |
| | 7) SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE WITH |
| | 2010 FBC ENERGY CONSERVATION CHAPTER 4 FOR EACH |
| | BUILDING. |
| | |
| | 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | BARREL TILE ROOFING AS REQUIRED BY DCA RULE 9N-3. |
| | SPECIFY THE FASTENING METHOD FROM THE PRODUCT APPROVAL |
| | THAT WILL BE USED TO INSTALL THE ROOF TILE. IF POLYFOAM |
| | WILL BE USED, SUBMIT PRODUCT APPROVALS FOR IT. FBC |
| | R905.3 |
| | |
| | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL WINDOW MULLIONS THAT WILL BE INSTALLED AS |
| | REQUIRED BY DCA RULE 9N-3. |
| | |
| | 10) THE PLANS SPECIFY IMPACT RESISTANT WINDOWS, |
| | HOWEVER, THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE |
| | FOR NON-IMPACT RESISTANT WINDOWS. FBC EXISTING BUILDING |
| | 606.4 AND FBC R301.2.1.2 REQUIRES GLAZED OPENINGS TO BE |
| | PROTECTED FROM WINDBOURNE DEBRIS. THE IMPACT PROTECTION |
| | DEVICES SHALL MEET THE LARGE MISSILE TEST OF ASTM E |
| | 1996, ASTM E 1886, SSTD 12 OR TAS 201, 202 AND 203 OR |
| | AAMA 506. SUBMIT PRODUCT APPROVALS FOR THE IMPACT |
| | PROTECTION DEVICES. INCLUDE A KEY PLAN AND AN |
| | INSTALLATION SCHEDULE WITH ANCHOR TYPE AND SPACING. |
| | |
| | 11) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE |
| | REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| | |