| Plan Review Notes For Permit 12080092 |
| Permit Number |
12080092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-06 13:29:50 | 12080092 | | | 6615 PAMELA LANE | | | ELECTRIC REVISION | | | | | | ELECTRICAL PANEL BOARDS MAY NOT BE LOCATED IN CLOSETS. | | | NEC 240.24 (D), 408.17 | | | PANEL BOARD ?A? REQUIRES A MAIN BREAKER. NEC 408.36 | | | MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED AND LOCATED | | | NEAR THE POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. | | | NEC 230.70, 230. 72 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|