| 2012-09-18 16:19:10 | RESIDENTIAL (R3) GARAGE CHANGE OF USE BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- SHEET A-1: DESIGN CRITERIA, ENGINEER SPECIFIES THAT |
| | THIS BUILDING IS LOCATED ON EXPOSURE "B". ACCORDING TO |
| | SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE THIS |
| | BUILDING IS LOCATED ON EXPOSURE "C". REVISE DESIGN |
| | CRITERIA INFORMATION AND DOORS/ WINDOWS DESIGN |
| | PRESSURES AS REQUIRED. |
| | |
| | 4- ENGINEER OF RECORD TO PROVIDE COMPLETE |
| | SPECIFICATIONS DETAILS ON PLANS SHOWING COMPLIANCE WITH |
| | THE OFFICE/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| | R302.6 OF 2010 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- SHEET A-2: |
| | A) PROPOSED FLOOR PLAN SPECIFIES OFFICE TRAY CEILING BY |
| | OWNER. ENGINEER OF RECORD TO PROVIDE COMPLETE FRAMING |
| | DETAILS. CLARIFY IF EXISTING TRUSSES OR ROOF RAFTERS |
| | ARE GOING TO BE CUT TO ALLOW FOR THE NEW TRAY CEILING. |
| | PROVIDE DETAILS SHOWING HOW THE EXISTING TRUSSES/ROOF |
| | RAFTERS ARE GOING TO BE REINFORCED TO KEEP THE |
| | STRUCTURAL STABILITY. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | B) BATHROOM CLOSET SHOWN ON THE PROPOSED FLOOR PLAN |
| | SHOWS THAT THE LAVATORY IS IN FRONT OF THE DOOR. |
| | THEREFORE, THE CLOSET IS NOT ACCESSIBLE. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) DOUBLE CASEMENT WINDOW SIZE AS SHOWN ON PLANS. NOA |
| | 07-0820.02 SUBMITTED DOESN'T COVER THE SIZE OF WINDOW |
| | SPECIFIED. |
| | |
| | B) FRENCH DOORS AS SHOWN ON PLANS. NOA 08-0821.09 |
| | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. VISIT THE |
| | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND |
| | RESUBMIT. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THE BAHAMA SHUTTERS) AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS TO FBC TO VERIFY THAT PRODUCT |
| | APPROVALS MEET THE CALCULATED DESIGN PRESSURES. |
| | |
| | 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| | INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. CLEARLY |
| | IDENTIFY WHICH SPECIFIC SHUTTERS FROM NOA 09-0122.07 |
| | SUBMITTED ARE GOING TO BE INSTALLED. AND SPECIFY |
| | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED BY THE |
| | ENGINEER. SEC. R301.2.1.4.3. |
| | |
| | 9- ACCORDING TO THE FLORIDA DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION (DBPR) THE CONTRACTOR NEEDS TO |
| | UPDATE HIS LICENSE. CONTRACTOR TO CONTACT DBPR TO |
| | UPDATE LICENSE STATUS. SEC. 105.1 CITY AMENDMENTS TO |
| | FBC. |
| | |