Plan Review Notes
Plan Review Notes For Permit 12071107
Permit Number 12071107
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-01 15:46:58RESIDENTIAL (R1) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PERMIT APPLICATION DESCRIBES REROOF OF FLAT DECK AT
 THE NORTH EAST END. NOT MORE THAN 25% OF THE ROOF AREA
 CAN BE RE-ROOFED. NEED TO RE-ROOF ENTIRE ROOF AS
 REQUIRED BY SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING.
 REVISE INFORMATION ON PERMIT APPLICATION AS REQUIRED
 AND UPDATE VALUATION ACCORDINGLY.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 11-0415.15 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. 1609 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. NEED TO UPDATE
 VALUATION. COORDINATE WITH ITEM #1 ABOVE.
  
 4- THERE ARE THREE DIFFERENT BUILDINGS ON THIS
 PROPERTY. CLEARLY IDENTIFY WHICH BUILDING IS THE ONE
 COVERED BY THIS PERMIT APPLICATION. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected].