| Plan Review Notes For Permit 12071107 |
| Permit Number |
12071107 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-01 15:46:58 | RESIDENTIAL (R1) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PERMIT APPLICATION DESCRIBES REROOF OF FLAT DECK AT | | | THE NORTH EAST END. NOT MORE THAN 25% OF THE ROOF AREA | | | CAN BE RE-ROOFED. NEED TO RE-ROOF ENTIRE ROOF AS | | | REQUIRED BY SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING. | | | REVISE INFORMATION ON PERMIT APPLICATION AS REQUIRED | | | AND UPDATE VALUATION ACCORDINGLY. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 11-0415.15 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO | | | MEET THE DESIGN PRESSURES OF SEC. 1609 FBC-BUILDING. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. NEED TO UPDATE | | | VALUATION. COORDINATE WITH ITEM #1 ABOVE. | | | | | | 4- THERE ARE THREE DIFFERENT BUILDINGS ON THIS | | | PROPERTY. CLEARLY IDENTIFY WHICH BUILDING IS THE ONE | | | COVERED BY THIS PERMIT APPLICATION. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | [email protected]. |
|