| Plan Review Notes For Permit 12070993 |
| Permit Number |
12070993 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-07 10:17:06 | FBC PLUMBING 2010 REVIEW #1 | | | DENIED: | | | | | | 1. BUSINESS OCCUPANCY WITH OVER 15 OCCUPANTS REQUIRES A | | | HIGH/LO DRINKING FOUNTAIN OR EQUAL (SEE EXCEPTION). | | | PLUMBING TABLE 403.1 (E) (F) | | | FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO | | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | | | | 2. FBC 107.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW | | | CRITERIA FOR BUILDINGS. (3) WATER SUPPLY PIPING. (13) | | | PLUMBING RISER. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|