| 2012-09-10 10:50:46 | BUILDING PLAN REVIEW |
| | PERMIT: 12070945 |
| | ADD: 550 S ROSEMARY # 151 |
| | CONT: RCC ASSOCIATES, INC. |
| | TEL: (561)856-6655 (NEYITA) |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | SEPT. 10/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) SHEETS A-7.1 DETAIL # 1, S-1 & S-2 ALL INDICATE |
| | STRUCTURAL WORK TO BE COMPLETED UNDER THIS PERMIT. |
| | FLORIDA S 553.71(7) CONSIDER THIS A THRESHOLD BUILDIING |
| | AND THE CLIENT WILL NEED TO PROVIDE A SPECIAL INSPECTOR |
| | TO PERFORM STRUCTURAL INSPECTIONS ON THE THRESHOLD |
| | BUILDING. |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. CONTRACT |
| | AGREEMENT MUST BE SUGNED BY ALL PARTIES. |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D) THREE SETS OF PLANS REQUIRED FOR THRESHOLD |
| | BUILDINGS. |
| | ------------------------------------------------------- |
| | ----------------------------------- |
| | NOTE: |
| | 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | ------------------------------------------------------- |
| | ------------------------------------- |
| | |
| | A (SOFT HOLD), WILL BE PUT ON THIS PROJECT ALL REVIEWS |
| | WILL CONTINUE THROUGH THE PLAN REVIEW PROCESS, JUST GET |
| | ISSUED UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY |
| | THE CHIEF BUILDING INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 1D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 1E)) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2-5A ) COMPLIED. |
| | 5B) PROVISO: EXTERIOR AWNINGS ARE TO BE REVIEWED UNDER |
| | SEPERATE PERMIT . 105.1. |
| | |
| | 6) 2010 FBC-B 806.3 FOAM PLASTIC.A-7.1, A-4.2 DETAILS 8 |
| | & 9 FOAM CROWN AND FAUX WOOD BEAMS. FOAM PLASTIC USED |
| | AS TTRIM IN ANY OCCUPANCY SHALL COMPLY WITH SECTION |
| | 2604.2.(1-4). THE RESPONCE INDICATES PAINTING ON A |
| | FX-100 FIRE RETARDANT COATING WITHIN THE TEST INDICATES |
| | THE ESTABLISHED SURFACE BURNING CHARACTERISTICS ARE |
| | ONLY APPLICABLE WHEN THE COATING MATERIAL IS APPLIED IN |
| | THE INDICATED NUMBER OF COATS, COVERAGE RATES, |
| | SUBSTRATES, OVERCOATS AND UNDERCOATS AS SPECIFIED IN |
| | THE PUBLISHED LITERATURE FROM UL. PLEASE NOTE THE TEST |
| | SUBJECT IS RED OAK TO BE USED AS FLOORING, NOT FOAM |
| | TRIM TO BE ATTACHED TO THE CEILING. |
| | PROVIDE TEST DOCUMENTS WITH FOAM AS THE SUBTRATE AND |
| | TESTED AS TRIM IN THE CEILING TYPE CONFIGURATION OR |
| | CROWN MOLDING IN A CORNER TEST. |
| | |
| | 7-8) COMPLIED. |
| | |
| | 9) PROVISO: WIND DESIGN PRESSURES ARE GOOD PRODUCT |
| | APPROVALS WILL COME IN AS A REVISION. THIS PLAN HAS |
| | BEEN APPROVED PROVISIONALLY. FAILURE TO CORRECT THE |
| | LISTED DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION |
| | WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT |
| | OF RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL |
| | REVIEWS WITH ASSOCIATED FEES BEFORE FRAMING INSPECTION. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) PROVISO: WIND DESIGN PRESSURES ARE GOOD PRODUCT |
| | APPROVALS WILL COME IN AS A REVISION. THIS PLAN HAS |
| | BEEN APPROVED PROVISIONALLY. FAILURE TO CORRECT THE |
| | LISTED DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION |
| | WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT |
| | OF RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL |
| | REVIEWS WITH ASSOCIATED FEES BEFORE FRAMING INSPECTION. |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | ( (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 11) COMPLIED. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |