| Plan Review Notes For Permit 12070945 |
| Permit Number |
12070945 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-09 12:46:36 | FBC PLUMBING 2010 REVIEW #1 | | | DENIED: | | | | | | 1. SHEET P-5: | | | 905.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 | | | INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE | | | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | 2. THE SERVICE SINK IS REQUIRED TO CONNECT TO THE | | | GREASE WASTE LINE. | | | 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE | | | REMOVAL DEVICES REQUIRED. | | | A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE | | | SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES | | | AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD | | | PREPARATION AREAS... | | | | | | | | | ****NOTE**** | | | FUEL GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE | | | APPLICATION, REVIEW, PERMIT, AND FEE REQUIRED FOR FUEL | | | GAS PERMIT. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|