| 2012-07-30 14:51:51 | 550 SOUTH ROSEMARY AVENUE - SUITE #148 |
| | PERMIT #12070945 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ****PROVISO**** SUBMIT REVISION |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | SHEET A2.3: INDICATE THE SMOKE AND FLAME SPREAD RATING |
| | OF THE CEILING DRAPERY. |
| | |
| | SHEET A-11.0: DOOR #101 - FOR ASSEMBLY OCCUPANCIES WITH |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE |
| | SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| | NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| | BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE (AND ONLY THE MAIN |
| | ENTRANCE) IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| | "THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| | OCCUPIED." SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. NOTE: A THUMB TURN STYLE LOCK IS NOT PERMITTED |
| | TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | SHEET A-11.0: DOOR #103A - NO OTHER LOCKS OR LATCHES |
| | ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |