| 2012-08-01 09:26:48 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- FLAT ROOF RAS 117 CALCULATIONS: | | | | | | A) ENGINEER TO REVISE THE RAS 117 CALCULATIONS. | | | ACCORDING TO SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL | | | THIS BUILDING IS LOCATED ON EXPOSURE "D" NOT "C". | | | REVISE CALCULATIONS AS REQUIRED. | | | | | | ***NOTE: THIS WAS NOTED ON THE FIRST REVIEW COMMENTS TO | | | AVOID ANY DELAYS. | | | | | | B) ENGINEER TO REVISE THE PERIMETER AND CORNER AREA | | | MINIMUM DIMENSION. ACCORDING TO FOOTNOTE ON FIGURE | | | R301.2(7) THE MINIMUM DIMENSION IS 4'-0" IN ALL CASES | | | NOT 3'-0". | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | [email protected] |
|