| Plan Review Notes For Permit 12070923 |
| Permit Number |
12070923 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-28 13:41:16 | PLANS DENIED | | | 1) PROVIDE HANGING DETAIL FROM THE ENGINEER FOR AIR | | | HANDLERS | | | SECTION 107 FBC 2010 | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | FLORIDA ENERGY CODE. | | | 3) SEPARATE APPLICATION ,PLANS AND PERMITS REQUIRED FOR | | | HOOD, COOLERS, FIRE SUPPRESSION AND HABACHI TABLES AND | | | DUCT | | | PER SECTION 107 FBC 2010 | | | 4) PROVIDE EQUIPMENT SCHEDULE FOR NEW EXHAUST FANS AND | | | NEW AIR HANDLERS PER SECTION 127 FBC 2010 | | | 5) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO | | | ROOF TIEDOWN | | | AND THE EXHAUST FAN TO CURB TIEDOWN PER SECTION 301.12 | | | WIND RESISTANCE FBC (M) 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|