2012-08-04 22:08:082727 HILLSBORO ROAD
 PERMIT #12070867
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 I AGREED TO NO PLANS FOR THIS SPRINKLER PERMIT. THE
 EXISTING SPRINKLERS ARE OVER 50 YEARS OLD AND JUST NEED
 TO BE REPLACED. NO PIPING OR VALVES ARE BEING REPLACED.
 I DO WANT THE CONTRACTOR TO CUT ONE SECTION OF BRANCH
 LINE TO VERIFY THERE IS NO CORROSION (MORE THAN NORMAL)
 OR MICROBES (MIC) AFFECTING THE PIPING. A LETTER FROM
 THE CONTRACTOR WILL BE NEEDED INDICATING THEIR
 FINDINGS.
  