| Plan Review Notes For Permit 12070821 |
| Permit Number |
12070821 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-31 11:23:02 | RESIDENTIAL (R2) CONCRETE ROOF TILE REPAIRS BUILDING | | | REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ENGINEER TO REVISE CALCULATIONS SUBMITTED. | | | A) REVISE THE MOMENT OF RESISTANCE CALCULATIONS FOR | | | FIELD AND PERIMETER ZONES. KEEP IN MIND THAT THE DESIGN | | | PRESSURES ARE NEGATIVE WHEN RUNNING THE CALCULATIONS. | | | SEC. 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | | | B) CHECK THE HEIGHT OF THE BUILDINGS. ACCORDING TO OUR | | | RECORDS BUILDINGS ARE FOUR STORIES HIGH. THEREFORE, | | | 30'-0" HEIGHT NEEDS TO BE REVISED. REVISE CALCULATIONS | | | AS REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | | | 2- FOR YOUR INFORMATION: REPAIRS THAT ARE MORE THAN 25% | | | OF THE ROOF AREA REQUIRE RE-ROOFING THE ENTIRE ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|