| Plan Review Notes For Permit 12070800 |
| Permit Number |
12070800 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-21 08:52:28 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2010 CODE FAMILY | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAYNE AHU LOOKS TO BE OVER AN AREA OF HARD CEILING. | | | FULL ACCESS FOR SERVICE AND/OR REPLACEMENT IS REQUIRED | | | PER FBC-M 306.1. | | | | | | 2. PROVIDE BALANCED RETURN FOR SYSTEMS WHERE A | | | CENTRALIZED RETURN IS UTILIZED AND CLOSED DOORS WILL | | | IMPEDE THE FREE FLOW OF RETURN AIR TO THE UNIT PER | | | FBC-M 601.4. | | | | | | 3. PROVIDE VENTILATION CALCULATIONS AND SHOW HOW | | | VENTILATION IS TO BE PROVIDED FOR ALL AREAS WHICH | | | CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M 403.1. | | | | | | 4. PROVIDE WIND RESISTANT ATTACHMENT DETAILS FOR THE | | | RTU AND ACCU PER FBC-M 301.12. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|