2012-08-21 08:52:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAYNE AHU LOOKS TO BE OVER AN AREA OF HARD CEILING.
 FULL ACCESS FOR SERVICE AND/OR REPLACEMENT IS REQUIRED
 PER FBC-M 306.1.
  
 2. PROVIDE BALANCED RETURN FOR SYSTEMS WHERE A
 CENTRALIZED RETURN IS UTILIZED AND CLOSED DOORS WILL
 IMPEDE THE FREE FLOW OF RETURN AIR TO THE UNIT PER
 FBC-M 601.4.
  
 3. PROVIDE VENTILATION CALCULATIONS AND SHOW HOW
 VENTILATION IS TO BE PROVIDED FOR ALL AREAS WHICH
 CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M 403.1.
  
 4. PROVIDE WIND RESISTANT ATTACHMENT DETAILS FOR THE
 RTU AND ACCU PER FBC-M 301.12.
  