2012-07-30 11:59:497000 SOUTH DIXIE HIGHWAY
 PERMIT #12070800
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PROJECT APPEARS TO HAVE THREE REHABILITATION
 CLASSES:
 (1) ADDITION
 (2) CHANGE OF OCCUPANCY (FRONT BUILDING ONLY - MOTEL
 OCCUPANCY TO BUSINESS OCCUPANCY)
 (3) LEVEL III ALTERATION WHEREBY MORE THAN 50% OF THE
 COMBINED BUILDING AREAS ARE BEING REHABILITED.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SHEET A-3.0 INDICATES THE USE OF THE SPACE AS BUSINESS
 OFFICES; HOWEVER, SHEET E-2 INDICATES THE SAME SPACES
 TO BE USED AS STORAGE AND RETAIL WHICH WOULD BE TREATED
 AS TWO SEPARATE OCCUPANCIES TYPES ALTOGETHER.
  
 THE MOTEL SUITES INDICATE INDIVIDUAL COOKING FACILITIES
 WHICH WOULD CLASSIFY THE BUILDING AS A MIXED-USE HOTEL
 AND APARTMENT OCCUPANCY. THE STRICTEST FIRE PROTECTION
 AND LIFE SAFETY PROVISIONS OF EACH OCCUPANCY WILL
 APPLY.
  
 PER THE LIFE SAFETY CODE (NFPA 101) SECTION 43.6.4.1,
 "IN A BUILDING WITH REHABILITATION WORK AREAS INVOLVING
 OVER 50 PERCENT OF THE AGGREGATE BUILDING AREA,
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED..IN
 ACCORDANCE WITH THE REQUIREMENTS OF OTHER SECTIONS OF
 THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE
 OCCUPANCY."
  
 PER NFPA 101 SECTION 30.3.5, "ALL APARTMENT BUILDINGS
 SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED, AUTOMATIC SPRINKLER SYSTEM."
  
 PER NFPA 101 SECTION 30.3.4.5, HARD-WIRED MULTI-STATION
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS, AND ON ALL LEVELS OF THE DWELLING
 UNIT, INCLUDING BASEMENTS.
  
 INDICATE IF LAUNDRY #37 IS DEDICATED TO ONE MOTEL SUITE
 OR IF THE LAUNDRY WILL BE USED BY ALL MOTEL GUESTS.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE BUILDING ADDRESSES VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  