2012-08-06 11:00:0312070800
 7000 S.DIXIE
 COMMERCIAL RENOVATION/ CHANGE OF USE
  
 PLEASE SPECIFY AN ELECTRICAL WIRING METHOD. NEC 110.8
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT. NEC 110.22, 110.16
 PLEASE INDICATE THE TYPE OF CEILING AND HEIGHT. THE
 HEIGHT OF CEILING FANS SHALL BE IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. NEC 110.3
 SMOKE ALARMS ARE REQUIRED FOR THE SLEEPING UNITS. FBC
 704.4.3
 RESIDENTIAL UNITS REQUIRE SOME ADDITIONAL RECEPTACLES.
 NEC 210.8, FBC 708.1
 UNDERGROUND SERVICE CONDUCTORS REQUIRE A WARNING
 RIBBON. NEC 300.5(D) (3)
  