| Plan Review Notes For Permit 12070800 |
| Permit Number |
12070800 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-06 11:00:03 | 12070800 | | | 7000 S.DIXIE | | | COMMERCIAL RENOVATION/ CHANGE OF USE | | | | | | PLEASE SPECIFY AN ELECTRICAL WIRING METHOD. NEC 110.8 | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | EQUIPMENT. NEC 110.22, 110.16 | | | PLEASE INDICATE THE TYPE OF CEILING AND HEIGHT. THE | | | HEIGHT OF CEILING FANS SHALL BE IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. NEC 110.3 | | | SMOKE ALARMS ARE REQUIRED FOR THE SLEEPING UNITS. FBC | | | 704.4.3 | | | RESIDENTIAL UNITS REQUIRE SOME ADDITIONAL RECEPTACLES. | | | NEC 210.8, FBC 708.1 | | | UNDERGROUND SERVICE CONDUCTORS REQUIRE A WARNING | | | RIBBON. NEC 300.5(D) (3) | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|