| Notes |
| Date |
Text |
| 2012-08-07 14:34:59 | PLANS DENIED | | | 1) PROVIDE CALCULATIONS OF HEATING AND COOLING LOADS | | | PER SECTION 503.2.1 2010 FLORIDA ENERGY CODE. | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | (FOR FRESH AIR) 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|