| Plan Review Notes For Permit 12070779 |
| Permit Number |
12070779 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-09 07:51:15 | PROVISO: | | | NOTES WHERE PLANS ARE INCORRECT: | | | SHEET A-3.0 | | | TABLE 601 FIRE RESISTANT RATINGS, PROVIDED: | | | STRUCTURAL FRAME INCLUDING TRUSSES INDICATED 1 HR | | | PROTECTED, SHEET A-3.0 USE OF DROPPED ACOUSTICAL CEIL | | | PER 2010 FBC COMPLYING WITH 808.1.1.1 NOT FIRE RATIED, | | | FIRE RATING COMPLIES WITH 808.1.1.2 . | | | | | | BEARING WALLS, EXTERIOR INDICATES A 4 HR RATING, | | | MISSING FOOTNOTE B OF TABLE 720.1(2) 3-1.3 USE | | | EQUIVALENT THICKNESS, 2 HRS UNLESS CELLS FILLED. | | | | | | |
|