2012-08-09 07:51:15PROVISO:
 NOTES WHERE PLANS ARE INCORRECT:
 SHEET A-3.0
 TABLE 601 FIRE RESISTANT RATINGS, PROVIDED:
 STRUCTURAL FRAME INCLUDING TRUSSES INDICATED 1 HR
 PROTECTED, SHEET A-3.0 USE OF DROPPED ACOUSTICAL CEIL
 PER 2010 FBC COMPLYING WITH 808.1.1.1 NOT FIRE RATIED,
 FIRE RATING COMPLIES WITH 808.1.1.2 .
  
 BEARING WALLS, EXTERIOR INDICATES A 4 HR RATING,
 MISSING FOOTNOTE B OF TABLE 720.1(2) 3-1.3 USE
 EQUIVALENT THICKNESS, 2 HRS UNLESS CELLS FILLED.
  
  