| Plan Review Notes For Permit 12070734 |
| Permit Number |
12070734 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-03 14:50:22 | 12070734 | | | 2301 OKEECHOBEE BLVD | | | SITE LIGHTING | | | | | | PLEASE HAVE THE ENGINEER CLARIFY THE FOLLOWING: | | | | | | THE SITE PLAN SHOWS THREE POLE TYPES. THE POLE | | | SPECIFICATIONS (TWO TYPES) DO NOT SEEM TO MATCH THE | | | FIXTURE OR POLE CONFIGURATIONS SUBMITTED. | | | | | | THE WIND LOAD EFFECTIVE PROJECTED AREA (EPA) FOR THE | | | POLES DOES NOT INCLUDE OR REFERENCE THE EPA FOR THE | | | FIXTURES AND FLOOD LIGHTS. PLEASE IDENTIFY THE POLE | | | TYPE SUITABLE FOR EACH FIXTURE. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|