2012-09-11 08:45:362010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTER-COASTAL WATERWAY, ACCORDING TO FBC R301.2.1.4.3
 THE EXPOSURE CATEGORY IS "D". PLEASE REVISE THE PLANS.
  
 2) SUBMIT A DRAINAGE PLAN THAT SHOWS THAT THE SURFACE
 WATER IS DIRECTED TO AN APPROVED COLLECTION POINT AS
 REQUIRED BY FBC R401.3.
  
 3) THE PLANS SHOW ATTIC VENTS FOR A VENTED ATTIC AND
 THE ENERGY CALCULATION FORM SPECIFIES A SINGLE ASSEMBLY
 UN-VENTED ATTIC. PLEASE REVISE SO THAT THE TWO ARE IN
 AGREEMENT. CITY AMENDMENTS 107.2.1
  
 4) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE USED IN THE
 UN-VENTED ATTIC. FBC R316
  
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE PRE-FAB FIREPLACE.
 CITY AMENDMENTS 107.2.1.3 & FBCR M1801.1
  
 6) SHOW COMPLIANCE WITH FBC R302.5.1 FOR THE DOOR
 BETWEEN THE GARAGE AND THE LIVING SPACE.
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE ARCH OPENINGS ON
 THE PLANS.
  
 8) SPECIFY THE WALL TO TRUSS CONNECTORS AND UPLIFT
 LOADS ON THE ROOF FRAMING PLANS. FBC R802.1.6.5
  
 9) THE PLANS CALL OUT (2) 3080 FRENCH DOORS AT THE
 MASTER BEDROOM AND A 5' - 2" OPENING DIMENSION IS
 SPECIFIED. PLEASE CLARIFY.
  
 10) THE COMPONENT AND CLADDING WALL PRESSURES ARE VULT
 (ULTIMATE DESIGN WIND SPEED) AND THE PRODUCT APPROVALS
 ARE BASED ON VASD (NOMINAL DESIGN WIND SPEED). BECAUSE
 OF THIS THE DESIGN PRESSURES IN THE PRODUCT APPROVALS
 FOR THE WINDOWS AND DOORS ARE LOWER THAN THE ONES
 SPECIFIED IN THE TABLE ON SHEET ONE. PLEASE REVISE THE
 TABLE. FBC R301.2.1.3
  
 11) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1
  
 12) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS REQUIRED
 BY DCA RULE 9N-3. ONLY ONE SET WAS SUBMITTED. CITY
 AMENDMENTS 107.1
  
 13) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS, THE 1/2 ROUND FIXED WINDOWS ABOVE
 THE FRENCH DOORS, THE ROOFING MATERIAL FOR THE FLAT
 ROOF. DCA RULE 9N-3
  
 14) THE FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED FOR
 THE OVERHEAD GARAGE DOOR #7768 IS FOR THE 2007 FBC.
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 2010 FBC
 FOR THESE DOORS. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]