| 2012-09-11 08:45:36 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE |
| | INTER-COASTAL WATERWAY, ACCORDING TO FBC R301.2.1.4.3 |
| | THE EXPOSURE CATEGORY IS "D". PLEASE REVISE THE PLANS. |
| | |
| | 2) SUBMIT A DRAINAGE PLAN THAT SHOWS THAT THE SURFACE |
| | WATER IS DIRECTED TO AN APPROVED COLLECTION POINT AS |
| | REQUIRED BY FBC R401.3. |
| | |
| | 3) THE PLANS SHOW ATTIC VENTS FOR A VENTED ATTIC AND |
| | THE ENERGY CALCULATION FORM SPECIFIES A SINGLE ASSEMBLY |
| | UN-VENTED ATTIC. PLEASE REVISE SO THAT THE TWO ARE IN |
| | AGREEMENT. CITY AMENDMENTS 107.2.1 |
| | |
| | 4) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| | SPRAY FOAM INSULATION THAT WILL BE USED IN THE |
| | UN-VENTED ATTIC. FBC R316 |
| | |
| | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND LISTING FOR THE PRE-FAB FIREPLACE. |
| | CITY AMENDMENTS 107.2.1.3 & FBCR M1801.1 |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R302.5.1 FOR THE DOOR |
| | BETWEEN THE GARAGE AND THE LIVING SPACE. |
| | |
| | 7) PROVIDE STRUCTURAL DETAILS FOR THE ARCH OPENINGS ON |
| | THE PLANS. |
| | |
| | 8) SPECIFY THE WALL TO TRUSS CONNECTORS AND UPLIFT |
| | LOADS ON THE ROOF FRAMING PLANS. FBC R802.1.6.5 |
| | |
| | 9) THE PLANS CALL OUT (2) 3080 FRENCH DOORS AT THE |
| | MASTER BEDROOM AND A 5' - 2" OPENING DIMENSION IS |
| | SPECIFIED. PLEASE CLARIFY. |
| | |
| | 10) THE COMPONENT AND CLADDING WALL PRESSURES ARE VULT |
| | (ULTIMATE DESIGN WIND SPEED) AND THE PRODUCT APPROVALS |
| | ARE BASED ON VASD (NOMINAL DESIGN WIND SPEED). BECAUSE |
| | OF THIS THE DESIGN PRESSURES IN THE PRODUCT APPROVALS |
| | FOR THE WINDOWS AND DOORS ARE LOWER THAN THE ONES |
| | SPECIFIED IN THE TABLE ON SHEET ONE. PLEASE REVISE THE |
| | TABLE. FBC R301.2.1.3 |
| | |
| | 11) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE |
| | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1 |
| | |
| | 12) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS REQUIRED |
| | BY DCA RULE 9N-3. ONLY ONE SET WAS SUBMITTED. CITY |
| | AMENDMENTS 107.1 |
| | |
| | 13) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE |
| | STRUCTURAL MULLIONS, THE 1/2 ROUND FIXED WINDOWS ABOVE |
| | THE FRENCH DOORS, THE ROOFING MATERIAL FOR THE FLAT |
| | ROOF. DCA RULE 9N-3 |
| | |
| | 14) THE FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED FOR |
| | THE OVERHEAD GARAGE DOOR #7768 IS FOR THE 2007 FBC. |
| | SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 2010 FBC |
| | FOR THESE DOORS. DCA RULE 9N-3 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |