Plan Review Notes
Plan Review Notes For Permit 12070700
Permit Number 12070700
Review Stop P
Sequence Number 1
Notes
Date Text
2012-08-03 14:36:16FBC PLUMBING 2010 REVIEW #1
 DENIED:
  
 1. THERE APPEAR TO BE TWO EXISTING PUBLIC USE WATER
 CLOSETS FOR WOMEN ON SHEET A010.
 FROM SHEET CS THE OCCUPANT LOAD FOR WOMEN IN THE PUBLIC
 AREA IS:
 A-2____ 39 WOMEN @ 1 PER 75 = .52 WATER CLOSET
 A-3___ 144 WOMEN @ 1 PER 65 = 2.21
 TOTAL REQUIRED FOR WOMEN 2.73 (3) WATER CLOSETS WOULD
 BE REQUIRED PER TABLE FBC PLUMBING 403.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  