| Plan Review Notes For Permit 12070700 |
| Permit Number |
12070700 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-03 14:36:16 | FBC PLUMBING 2010 REVIEW #1 | | | DENIED: | | | | | | 1. THERE APPEAR TO BE TWO EXISTING PUBLIC USE WATER | | | CLOSETS FOR WOMEN ON SHEET A010. | | | FROM SHEET CS THE OCCUPANT LOAD FOR WOMEN IN THE PUBLIC | | | AREA IS: | | | A-2____ 39 WOMEN @ 1 PER 75 = .52 WATER CLOSET | | | A-3___ 144 WOMEN @ 1 PER 65 = 2.21 | | | TOTAL REQUIRED FOR WOMEN 2.73 (3) WATER CLOSETS WOULD | | | BE REQUIRED PER TABLE FBC PLUMBING 403.1 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|