Plan Review Notes
Plan Review Notes For Permit 12070700
Permit Number 12070700
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-07-31 12:46:42600 NORTHPOINT PARKWAY
 PERMIT #12070700
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO FIRE ALARM APPLIANCES, EXIT SIGNS OR EMERGENCY
 LIGHTING LAYOUTS PROVIDED.
  
 SEPARATE SUB-PERMITS REQUIRED FOR MODIFICATION OF
 EXISTING FIRE ALARM AND FIRE SPRINKLER SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  