2012-08-06 14:47:42BUILDING PLAN REVIEW
 PERMIT: 12070699
 ADD: 600 NORTHPOINT PARKWAY
 CONT: CORPORATE PROPERTY SEERVICES INC.
 TEL: (954)426-5144
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE 2010 FBC-ACCESSIBILITY CODE TABLE 224.2 GUEST
 ROOMS WITH MOBILITY FEATURES INDICATES A TOTAL OF (7)
 SUITES SHOULD MEET THIS REQUIREMENT. SHEET G-001 WILL
 MEET THIS REQUIREMENT BUT THE ACCESSIBLE UNITS ON THE
 2ND FLOOR ARE NOT DEPICTED AS ACCESSIBLE UNITS ON SHEET
 A-112.
  
 2) PLEASE PROVIDE CODE COMPLIANCE WITH:
 2010 FBC-ACCESSIBILITY 224.5 DISPERSION.
 GUEST ROOMS REQUIRED TO PROVIDE MOBILITY FEATURES
 COMPLYING WITH 806.2 AND GUEST ROOMS REQUIRED TO
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3
 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF GUEST
 ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF GUEST
 ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES COMPARABLE
 TO THE CHOICES PROVIDED TO OTHER GUESTS. WHERE THE
 MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO COMPLY WITH
 806 IS NOT SUFFICIENT TO ALLOW FOR COMPLETE DISPERSION,
 GUEST ROOMS SHALL BE DISPERSED IN THE FOLLOWING
 PRIORITY: GUEST ROOM TYPE, NUMBER OF BEDS, AND
 AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED TO PROVIDE
 MOBILITY FEATURES COMPLYING WITH 806.2 SHALL ALSO
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3.
 NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL BE
 USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
  
 3) THE COVERSHEET CS-GR CODE DATA INDICATES THIS
 BUILDING WAS BUILT AS A TYPE V UNPROTECTED PER
 DOCUMENTS STATING 1987. THE 2004 FBC BUILDING TYPES
 CHANGED, THE PREVIOUS CODES A TYPE V-UNPROTECTED BECAME
 A TYPE IIIB IN THE 2004 FBC TO THE CURRENT VERSION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved