| Plan Review Notes For Permit 12070697 |
| Permit Number |
12070697 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-24 11:38:20 | 12070697 | | | 2400 S. DIXIE | | | ADA RESTROOM CONSTRUCTION | | | | | | DEPTH OF WORKING SPACE IN FRONT OF EXISTING PANEL | | | BOARDS MUST BE AT LEAST 36 INCHES. NEC 110.26 | | | | | | OVERCURRENT DEVICES AND ENCLOSURES SHOULD NOT BE | | | LOCATED ADJACENT TO A MOP SINK. NEC 240.32, 312.2 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|