| 2012-07-24 11:05:40 | 12070649 | | | 501 FERN ST # C1 | | | COMMERCIAL SHELL | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. | | | NEC 230.2, 230.71, 230.72 | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|