| Plan Review Notes For Permit 12070644 |
| Permit Number |
12070644 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-19 11:43:28 | ***PROVISO**** | | | | | | REVIEWED FOR FOUNDATION PERMIT ONLY. | | | | | | REVISED PLUMBING DRAWINGS REQUIRED: | | | 1. THE NEW MENS ROOM #120 DOES NOT HAVE A STALL | | | COMPLYING WITH FBC 2010 ACCESSIBILITY 213.3.1 TOILET | | | COMPARTMENTS AND 604.8.1. SEE FIGURE 604.8.1.6 | | | | | | 2. ONE URINAL WILL BE REQUIRED TO BE MOUNTED AT A MAX. | | | OF 17" AFF TO RIM.- 213.3.3 | | | | | | 3. THE CENTER OF THE HC LAV ON SHEET A-8 WILL BE 1'-3" | | | IF THE STALL IS THE MIN. 7'-1" | | | | | | 4. A HI/LO DRINKING FOUNTAIN IS LISTED ON P-1 BUT NOT | | | FOUND ON THE PLUMBING DRAWING. | | | | | | 5. HOT WATER IS REQUIRED AT THE SERVICE SINK AND | | | KITCHEN SINK. FBC 2010 PLUMBING 607.1 | | | | | | 6. A VENT IS REQUIRED FOR THE GRINDER PUMP PER | | | MANUFACTURERS INSTRUCTIONS. | | | | | | 7. THE KITCHEN SINK AND SERVICE SINK ARE SHOWN | | | CONNECTING TO A WET VENT. FIXTURES OTHER THAN BATHROOM | | | FIXTURES ARE REQUIRED TO CONNECT DOWNSTREAM OF THE WET | | | VENT SYSTEM. | | | FBC 2010 PLUMBING 909.1 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 |
|