| 2012-07-31 16:11:01 | BUILDING PLAN REVIEW |
| | PERMIT: 12070625 |
| | ADD: 3111 45TH ST |
| | CONT: SKYHIGH SIDING & ROOFING |
| | TEL: (772)631-3600 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ROOF FRAMING PLAN SHEET S2 INDICATES THE WIND DESIGN |
| | CRITERIA IS FIGURED WITH A "B" EXPOSURE, PLEASE SEE |
| | 2010 FBC-B: |
| | 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A GROUND SURFACE |
| | ROUGHNESS WITHIN EACH 45-DEGREE (0.79 RAD) SECTOR SHALL |
| | BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE AS |
| | DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES DEFINED |
| | BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE |
| | CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| | |
| | SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| | OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET |
| | (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND |
| | GRASSLANDS.THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO |
| | ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE |
| | TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET |
| | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE |
| | ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN |
| | 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN |
| | THE UPWIND DIRECTION... |
| | PLEASE UPDATE PLANS AND WALL CONNECTIONS ACCORDINGLY. |
| | |
| | 2) THE PERMIT APPLICATION UNDER DESCRIPTION OF WORK |
| | INCLUDES AHNGING DRYWALL, ELECTRICAL , PLUMBING AND A/C |
| | WORK, BUT NO PLANS ARE PROVIDED FOR THE INTERIOR WORK. |
| | THE PLANS INDICATE A LEVEL ONE ALTERATION TO GO BACK |
| | WITH EXACT LAYOUT BUT NOTHING HAS BEEN PROVIDED |
| | INDICATING CODE COMPLIANCE. THE OTHER ISSUE IS NO |
| | ENERGY CALCULATIONS AND MECHANICAL EQUIPMENT WAS |
| | SUBMITTED. |
| | |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE |
| | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| | CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE |
| | PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS |
| | LAYOUT; ALL FENESTRATION PENETRATIONS; |
| | FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL |
| | EXTERIOR ELEVATIONS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | FIRE ACCESS |
| | SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| | LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| | ELEVATIONS |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | RISER DIAGRAM |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING |
| | REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | WIND REQUIREMENTS NO PRODUCT APPROVALS WERE SUBMITED |
| | FOR WINDOWS & DOORS |
| | BUILDING ENVELOPE |
| | FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, |
| | INCLUDING LOWEST FLOOR |
| | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT |
| | MATERIALS |
| | ROOF SYSTEMS NO PRODUCT APPROVALS WERE SUBMITTED |
| | |
| | 3) FOR A ROOFING PERMIT A ROOFING CONTRACTOR WILL NEED |
| | TO APPLY FOR A ROOFING PERMIT. F S 489.113(3) |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |