Plan Review Notes
Plan Review Notes For Permit 12070623
Permit Number 12070623
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-07-24 10:12:021800 SOUTH AUSTRALIAN AVENUE
 PERMIT #12070623
 FIRE ALARM SYSTEM
  
 REVIEW COMMENTS: FIRE DEPARTMENT
 FIRE ALARM SYSTEM NEEDS TO BE INTERLOCKED WITH ALL
 MAGNETIC LOCKING DOORS LOCATED ON THE FIRST FLOOR. PER
 SECTION 7.2.1.6.2 (NFPA 101) ACCESS-CONTROLLED EGRESS
 DOOR ASSEMBLIES DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE EQUIPPED WITH AN APPROVED
 ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM, PROVIDED
 THAT ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM SHALL AUTOMATICALLY UNLOCK THE DOOR
 LEAVES IN THE DIRECTION OF EGRESS, AND THEY SHALL
 REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
  
 PROVIDE A NOTE ON THE PLANS INDICATING THE VACANT
 TENANT SPACES WILL NEED TO HAVE NOTIFICATION APPLIANCES
 ADDED TO THE SUITE BEFORE OCCUPANCY IS PERMITTED.
  
 THE SUBMITTED PLANS INDICATE AUDIBLE-ONLY NOTIFICATION
 APPLIANCES ADDED TO THE EXISTING NON-CODE COMPLIANT
 FIRE ALARM SYSTEM. PER SECTION 9.6.3.5 (NFPA 101)
 NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE
 AUDIBLE AND VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE ALARM CODE. PER SECTION 1.3.6.4 (NFPA 1)
 NEWLY INTRODUCED EQUIPMENT, MATERIALS, AND OPERATIONS
 REGULATED BY THIS CODE SHALL COMPLY WITH THE
 REQUIREMENTS FOR NEW CONSTRUCTION OR PROCESSES.
  
 PER NFPA 72, VISUAL FIRE ALARM NOTIFICATION SHALL BE
 PROVIDED IN ALL PUBLIC AND COMMON USE AREAS SUCH AS
 RESTROOMS, CORRIDORS, CONFERENCE ROOMS, ETC.
  
 PER SECTION 9.6.1.3 (NFPA 101) A FIRE ALARM SYSTEM
 REQUIRED FOR LIFE SAFETY SHALL BE INSTALLED, TESTED,
 AND MAINTAINED IN ACCORDANCE WITH THE APPLICABLE
 REQUIREMENTS OF 2007 EDITION NFPA 72, NATIONAL FIRE
 ALARM AND SIGNALING CODE, UNLESS IT IS AN "APPROVED"
 EXISTING INSTALLATION, WHICH SHALL BE PERMITTED TO BE
 CONTINUED IN USE. THE EXISTING INSTALLATION IS NOT
 APPROVED BY THE FIRE DEPARTMENT.
  
  
 NOTES:
 IT WAS OBSERVED DURING A FIRE INSPECTION (CONDUCTED
 02/09/11) THAT THE FIRE ALARM SYSTEM WAS PROVIDING
 INADEQUATE NOTIFICATION. PER SECTION 9.6.3.7 (NFPA 101)
 AUDIBLE FIRE ALARM NOTIFICATION APPLIANCES SHALL BE OF
 SUCH CHARACTER AND SO DISTRIBUTED AS TO BE EFFECTIVELY
 HEARD ABOVE THE AVERAGE AMBIENT SOUND LEVEL THAT EXISTS
 UNDER NORMAL CONDITIONS OF OCCUPANCY.
  
 THE EXISTING FIRE ALARM SYSTEM DOES NOT COMPLY WITH
 CODE REQUIREMENTS THAT WERE IN EFFECT AT THE TIME OF
 INSTALLATION (1985); THEREFORE, THE FIRE ALARM SYSTEM
 DEFICIENCIES WILL NEED TO BE CORRECTED AND THE SYSTEM
 IMPROVED TO PROVIDE THE BUILDING OCCUPANTS WITH AN
 ACCEPTABLE LEVEL OF NOTIFICATION IN A FIRE EVENT.
  
 THE FLORIDA ADMINISTRATIVE CODE (CHAPTER 69A-48) FIRE
 SAFETY STANDARDS FOR FIRE ALARM SYSTEMS (69A-48.002)
 INDICATES, "THESE RULES APPLY TO BOTH NEW AND EXISTING
 FIRE ALARM SYSTEMS AS OF THE EFFECTIVE DATE OF THE
 RULE. THOSE SYSTEMS WHICH WERE BASED ON PRODUCT AND
 ENGINEERING PRACTICES RECOGNIZED AS BEING ACCEPTABLE AT
 THE DATE OF INSTALLATION BUT ARE NOT IN ARE NOT IN
 COMPLIANCE WITH CURRENTLY ADOPTED STANDARDS MAY
 CONTINUE IN USE, PROVIDED THEY ARE FUNCTIONAL AND
 "APPROVED" BY THE AUTHORITY HAVING JURISDICTION." IN
 THIS CASE, THE AUTHORITY HAVING JURISDICTION (WPB FIRE
 RESCUE), HAS INDICATED THAT THE EXISTING SYSTEM IS NOT
 "APPROVED."
  
 PER SECTION 3.2.1 (NFPA 101) "APPROVED" IS DEFINED AS
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
 SECTION 3.2.2 (NFPA 101) DEFINES "AUTHORITY HAVING
 JURISDICTION" (AHJ) AS AN ORGANIZATION, OFFICE, OR
 INDIVIDUAL RESPONSIBLE FOR ENFORCING THE REQUIREMENTS
 OF A CODE OR STANDARD, OR FOR APPROVING EQUIPMENT,
 MATERIALS, AN INSTALLATION, OR A PROCEDURE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  
  
  
  