| 2012-08-26 17:36:56 | 815 33RD STREET |
| | PERMIT #12070599 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ***THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION FROM |
| | FAMILY DAY-CARE HOME (3-6 CHILDREN) TO GROUP DAY-CARE |
| | HOME (7-12 CHILDREN)*** |
| | |
| | THERE SHALL BE NO MORE THAN 3 CHILDREN THAT ARE |
| | 24-MONTHS OF AGE OR YOUNGER, THAT WILL BE CARED FOR AT |
| | ANY ONE TIME. |
| | |
| | PROVIDE ESCAPE WINDOWS FOR ROOM #1, #2 AND #3. |
| | (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES |
| | IN HEIGHT, AND 5.7 SQ.FT. IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN |
| | 44-INCHES ABOVE THE FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE |
| | REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS |
| | THAN 20-INCEHS TO PASS FULLY THROUGH THE OPENING. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO FINAL FIRE INSPECTION. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |