| 2012-07-23 17:20:25 | 12070599 | | | 815 33RD ST. | | | DAYCARE | | | | | | PLEASE PROVIDE AN ELECTRICAL RECEPTICAL PLAN FOR THE | | | FACILITY. NEC 215.5 | | | A SMOKE ALARM IS REQUIRED. FBC 436.7.2 | | | RECEPTACLES IN THE BATHROOMS AND KITCHEN AREAS SHALL BE | | | GFCI PROTECTED. NEC 210.8 | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.14 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|