| 2012-07-30 10:08:49 | BUILDING PLAN REVIEW |
| | PERMIT: 11050812 |
| | ADD: 815 33RD ST |
| | CONT: TO BE DETERMINED |
| | TEL: (561)839-0700 |
| | |
| | 2010 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | 2010/09 FBC-B 313.2.2 GROUP DAY CARE HOME. A GROUP DAY |
| | CARE HOME IS A DAY-CARE HOME IN WHICH AT LEAST SEVEN |
| | BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, |
| | AND SUPERVISION BY OTHER THAN THEIR RELATIVE(S) OR |
| | LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS PER DAY WITH |
| | NO MORE THAN THREE CLIENTS INCAPABLE OF |
| | SELF-PRESERVATION. |
| | |
| | 1ST REVIEW |
| | |
| | 1) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE |
| | SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE |
| | CLOSET. |
| | |
| | 2) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL |
| | BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM |
| | THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL |
| | BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 3) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE |
| | NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY |
| | WITH SECTION 715.3. |
| | |
| | 4) PLANS DO NOT MAKE IT CLEAR IF THE THREE BEDROOMS ARE |
| | TO BE PART OF THE DAY CARE HOME, IF SO PLEASE COMPLY |
| | WITH : |
| | |
| | 436.10.5 SMOKE DETECTION SYSTEMS. |
| | |
| | 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN |
| | ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT |
| | REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED |
| | WITHIN DAY CARE HOMES. |
| | |
| | EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN |
| | ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE |
| | SAME MANNER SHALL BE PERMITTED. |
| | |
| | 436.10.5.2 WHERE THE DAY CARE HOME IS LOCATED WITHIN A |
| | BUILDING OF ANOTHER OCCUPANCY, ANY CORRIDORS SERVING |
| | THE DAY CARE HOME SHALL BE PROVIDED WITH A COMPLETE |
| | SMOKE DETECTION SYSTEM INSTALLED IN ACCORDANCE WITH |
| | NFPA 72. |
| | |
| | 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED |
| | BY THE BUILDING ELECTRICAL SYSTEM. |
| | |
| | 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE |
| | PROVIDED IN ALL ROOMS USED FOR SLEEPING. |
| | |
| | 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED |
| | WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA, |
| | THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| | ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING |
| | UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND. |
| | |
| | 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN |
| | INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA |
| | AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM. |
| | REMOTE ANNUNCIATION SHALL BE PERMITTED. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |