| Plan Review Notes For Permit 12070596 |
| Permit Number |
12070596 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-18 16:58:13 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ACCORDING TO HOUSE RECORDS EXISTING HOUSE WAS BUILT | | | WITH SHINGLES AS THE ROOF COVER SHINGLES NOT CONCRETE | | | TILE. PROVIDE ENGINEERING SHOWING THAT STRUCTURE WILL | | | SUPPORT THE CONCRETE TILE ADDITIONAL LOAD. SEC. | | | 107.2.1.3 CITY AMENDMENTS TO FBC. PROVIDE 2 COPIES WITH | | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTE. | | | | | | 2- FLAT ROOF: | | | A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 09-0224.01 SUBMITTED. NEED THE CALCULATIONS TO MEET THE | | | DESIGN PRESSURES AS REQUIRED BY SEC. R301.2.1.4.3 OF | | | 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|